Appendix A – Setting Up Network Interfaces 

 

Sageon II Bulk Product Manual 

 

 

PM990-5201-00, Issue 6 

7-4 

*** basic parameters 
Hardware: Ethernet Autodetect 
IP addr 192.168.000.098, no gateway set 
 
***************** Channel 1 ***************** 
Baudrate 09600, I/F Mode 4C, Flow 00 
Port 10001 
Remote IP Adr: --- none ---, Port 00000 
Connect Mode: C0  Disconn Mode: 00 
Flush   Mode: 00 
 
Change Setup  : 0 Server configuration 
                1 Channel 1 configuration 
                7 Factory defaults 
                8 Exit without save 
                9 Save and exit                Your choice ? 
 
5. Select an option on the menu by entering the number of the option in the 

Your choice 

? field and pressing 

Enter

 
6. To enter a value for a parameter, type the value and press 

Enter

, or to confirm a current value, just press 

Enter

 
7. When you are finished, save the new configurations (option 

9

). The unit will reboot. 

7.2.4

 

Server Configuration (Network Configuration) 

These are the unit’s basic network parameters. The following parameters are displayed when you select login into 
the unit: 

 
*** basic parameters 
Hardware: Ethernet Autodetect 
IP addr 192.168.000.098, no gateway set 
 
Select 0 and press Enter to configure the Lantronix Interface Server’s basic parameters  

IP Address 

The IP address must be set to a unique value in your network.  

Note: Lantronix Interface cannot connect to the network if the assigned IP address is already in use by another 
device. 

 

Gateway Address 

The gateway address, or router, allows communication to other LAN segments. The gateway address should be the 
IP address of the router connected to the same LAN segment as the 

Lantronix Interface

Note: 

The gateway address must be within the local network. 

 

Subnet Mask 

A netmask defines the number of bits taken from the IP address that are assigned for the host section. 

 
Note: 

Class A: 24 bits; Class B: 16 bits; Class C: 8 bits. 

 
The 

Lantronix Interface 

prompts for the number of host bits to be entered, then calculates the netmask, which is 

displayed in standard decimal-dot notation when the saved parameters are displayed (for example, 255.255.255.0). 

 

 Lantronix, Inc, 2002, all rights reserved, used herein by permission from Lantronix. 

 
 

Содержание Sageon II

Страница 1: ...nual PM 990 5201 00 Issue 6 sageon2_48 man pdf UNIPOWER LLC 3900 Coral Ridge Drive Coral Springs FL 33065 United States Tel 954 346 2442 Fax 954 340 7901 Email customer services unipowerco com Web sit...

Страница 2: ......

Страница 3: ...of shipment open the container and inspect the contents for damage If it is necessary to move or otherwise handle the shipment refer to the next section Handling for instructions and warnings Unpack t...

Страница 4: ...wn in italic in the label drawing below in all correspondence with UNIPOWER A sample nameplate is shown below 225 8001 00 SAGEON II POWER MODULE PART NUMBER 110 5201 INPUT RATING 85 300VAC 18A max 45...

Страница 5: ...bited Copyright UNIPOWER LLC 2015 DISCLAIMER Data descriptions and specifications presented herein are subject to revision by UNIPOWER LLC without notice While such information is believed to be accur...

Страница 6: ...ANSION MODULES 3 10 4 COMMISSIONING 4 1 5 OPERATION 5 1 5 1 SUMMARY OF CONTROLLER FRONT PANEL CONTROLS 5 1 5 2 CONTROLLER COMPONENTS 5 1 5 2 1 Alpha numeric Display 5 1 5 2 2 Front Panel Pushbuttons 5...

Страница 7: ...board connections 2 4 Figure 3 1 Mount points for securing Power Module in a rack 3 1 Figure 3 2 AC Feed Terminations 3 2 Figure 3 3 Single Phase feed phase to neutral 3 3 Figure 3 4 Single Phase fee...

Страница 8: ......

Страница 9: ...ivalent standard For open rack use the back of the magazine must be fully enclosed by its covers and the AC wiring terminations must be protected by either a grounded casing or an enclosure that provi...

Страница 10: ......

Страница 11: ...sed The Power Module provides the following integrated features Bulk power N 1 redundant rectifiers battery charge current limiting opt short circuit and reverse polarity protection battery temperatur...

Страница 12: ...Configuration Sageon II Bulk Product Manual PM990 5201 00 Issue 6 2 2 Figure 2 3 400A Bulk Power with AC Breakers Figure 2 4 600A Bulk Power with AC Breakers...

Страница 13: ...ribbon 7 Standalone system voltage connection Controller power and voltage sensing 8 Load circuit breaker trip detection circuitry connection Notes Devices and cable connections are pre wired as part...

Страница 14: ...Figure 2 7 Alarm relay board connections The alarm relay board is installed on the side of the Power module such that Relay 5 is on the top when viewed from the rear of the metalwork Each alarm is us...

Страница 15: ...ilarly the energy hazard associated with the batteries connected to the DC bus must be addressed with appropriately insulated tools and other measures to prevent accidental short circuits to the DC bu...

Страница 16: ...feed is individually protected and the installer is only required to connect a single AC supply 1 phase to the AC DIN rail terminations 3 3 MAINS CONNECTIONS Figure 3 2 AC Feed Terminations 3 3 1 Fac...

Страница 17: ...Installation Sageon II Bulk Product Manual PM990 5201 00 Issue 6 3 3 Figure 3 3 Single Phase feed phase to neutral Figure 3 4 Single Phase feed phase to phase...

Страница 18: ...Installation Sageon II Bulk Product Manual PM990 5201 00 Issue 6 3 4 Figure 3 5 split Single Phase feed phase to neutral Figure 3 6 Y Three Phase feed connected rectifiers phase to phase...

Страница 19: ...Installation Sageon II Bulk Product Manual PM990 5201 00 Issue 6 3 5 Figure 3 7 Y three Phase feed phase to neutral Figure 3 8 three Phase feed phase to phase...

Страница 20: ...tion Sageon II Bulk Product Manual PM990 5201 00 Issue 6 3 6 Figure 3 9 Y three phase feed Single Phase to rectifiers phase to phase Figure 3 10 Y Three Phase Feed Single Phase to Rectifiers phase to...

Страница 21: ...ses Other arrangements for 3 phase Y with similar levels of protection are also possible as shown below The voltage rating of the arrestor should be selected based on the maximum AC voltage likely to...

Страница 22: ...s Locate the ambient sensor close to the intake air zone of the Power Module Locate the battery sensor on a battery block in the middle Module of the battery bank likely hot zone 3 7 AUXILIARY RELAY C...

Страница 23: ...a rate 9600bps termination of the line with resistors generally is not required However if high rate of data corruption is experienced slow data update in monitoring program line termination resistors...

Страница 24: ...All boards are factory wired and allow for easy customer connection access Figure 3 14 AC Option Box Rear View screens removed for clarity 3 12 ADDING AUXILIARY EXPANSION MODULES Modules such as the S...

Страница 25: ...attery charging current limit to 10 of the Ah rating i e if 150Ah battery is used set the limit to 15A this value can be adjusted later to meet your specific charging requirements In many cases these...

Страница 26: ......

Страница 27: ...parameter press ENTER the value will flash on and off To increase the number press INC to decrease the number press DEC When the desired number is on the screen press ENTER again To change parameters...

Страница 28: ...rd must be programmed Once that is done security can be enabled 5 3 1 1 Entering a password to gain access to parameters change When the security function is active any changes to the system settings...

Страница 29: ...act failure A No Demand Control loop in RECTIFIER not in normal state A H S Temp High RECTIFIER heatsink temperature too high where available A Temp Sensor Fail Temp sensor in RECTIFIER faulty S C or...

Страница 30: ...ected or failure A Batt I Limit Battery charging current is being limited to preset value A Bat Sym Alarm Battery discharge currents from battery strings not sharing load equally A Earth Leak Alarm Ea...

Страница 31: ...etup Press ENTER Modify Value up down ENTER to accept Press ENTER to begin flashing display and LEDs Test Indicators Press ENTER ENTER System information including controller software version S N and...

Страница 32: ...Value up down ENTER to accept ENTER Phone 3 0398887788 Modify Value up down ENTER to accept ENTER Phone 3 Cont 2323 Modify Value up down ENTER to accept ENTER Audio Alarm Off INC DEC toggles state EN...

Страница 33: ...4 cells Modify Value up down ENTER to accept ENTER Number of battery banks BCM Batteries 1 Modify Value up down ENTER to accept ENTER Cell Vhi Alarm 2 50V Modify Value up down ENTER to accept ENTER Ce...

Страница 34: ...not be adjusted here Equalise Voltage SMR Default SMR Equalise 56 5V Cannot be adjusted here ENTER SMR voltage above which alarm flagged SMR V high Alarm 57 0V Modify Value up down ENTER to accept ENT...

Страница 35: ...Battery Rating 500Ah Modify Value up down ENTER to accept ENTER Battery Temperature compensation BTC Coeff 3 2 mV C C Modify Value up down ENTER to accept Variable from 0 to 6 0mV C C If BTC not Off...

Страница 36: ...ion EQ Duration 3 hours Modify Value up down ENTER to accept ENTER Periodic equalisation charging trigger EQ Period 12 Weeks Modify Value up down ENTER to accept Set to zero to disable ENTER Manual co...

Страница 37: ...ting to Closed or Auto Power up the rectifiers and reduce the load until the bus voltage increases to the float voltage Load or Battery circuit breaker alarm does not set when the breaker is opened or...

Страница 38: ...A rectifier is indicating RECTIFIER Off or No Response on the Controller RECTIFIER display An AC failure to the rectifier is the most likely cause While the rectifier internal power rails are still a...

Страница 39: ...rical interference where possible EEPROM Fail alarm for the Controller is activated Corrupted data found on the backplane EEPROM that is outside the allowable data range similar to RECTIFIER corruptio...

Страница 40: ......

Страница 41: ...new IP address Select correct network class Click Set IP Address button The process takes several seconds to complete and the progress is indicated below IP address field When completed a dialog box...

Страница 42: ...just press Enter if N press Y followed by enter Next item will be Gateway IP address nnn Enter assigned gateway address then press Enter at each item until set up menu is shown again Terminate Telnet...

Страница 43: ...P address you just set is temporary and will revert to the default value when the unit s power is reset unless you log into the unit and store the changes permanently Refer to the chapter on configura...

Страница 44: ...to the unit basic parameters Hardware Ethernet Autodetect IP addr 192 168 000 098 no gateway set Select 0 and press Enter to configure the Lantronix Interface Server s basic parameters IP Address The...

Страница 45: ...t Can sustain short circuit at output terminals indefinitely Reverse Battery Polarity Internal fuse at output of RECTIFIER High Voltage Shutdown Rectifier shuts down if output exceeds programmed overv...

Отзывы: