Operation
Sageon II Bulk Product Manual
PM990-5201-00, Issue 6
5-4
Alarm Name
Comments
LED
Battery Disch
Batteries are discharging
A
Disch Tst Fail
Battery discharge test failed to reach a programmed end point
A
Bat Disch Low
Alarm flags only if the system voltage falls below Discharge Alarm level while
the battery is discharging
A
Lo Electrolyte
Alarm generated for NiCad batteries using special sensor and software
A
RECTIFIER Comms Fail
One or more of RECTIFIERs are not responding
A
Amb Temp High
Ambient temperature higher than preset limit
A
Batt Temp High
Battery temperature higher than preset limit
A
Batt Temp Sens
Battery temperature sensor not connected or failure
A
Batt I-Limit
Battery charging current is being limited to preset value
A
Bat Sym Alarm
Battery discharge currents from battery strings not sharing load equally
A
Earth Leak Alarm
Earth leakage current greater than the limit set
A
Equalize
System is in equalize mode
A *
R = red LED on
A = amber LED flashing
* not flashing
5.3.4
User programmable relay functions
Units are shipped with factory default relay assignments (see below). The relay logic of the default settings is contact closure
on an active alarm. Relay functions can be re-assigned only from a PC running monitoring program Sageview (either
through the front panel USB or remote communications port). Refer to Sageview Help for instructions.
Relay Default Assignments
1
2
3
4
5
Not Assigned
Not Assigned
HV Shutdown
General Alarm
RECTIFIER
Shutdown
Customer Relay Assignments
(User to complete)