Operation
Sageon II Bulk Product Manual
PM990-5201-00, Issue 6
5-8
5.4.2
RECTIFIER Menu (Rectifier Specific Functions)
The RECTIFIER Float and Equalize voltages are the default values set in the rectifier that will be used if the Controller fails
to operate. They are a copy of the raw values set in the BATTERY menu without battery temperature compensation and
system drop adjustments.
5.4.3
Alarm Log
25.2A 54.3V
FL
SMR Button
ENTER
SMR software version
(
)
SMR1
13.2A 58°C
SMR1
S/W 137901
DEC
SMR Electronic Serial #
S/N
0102050500012
INC
ENTER
Additional screens if more
(
)
SMR2
:
SMR2
:
SMRs are declared
S/N
:
Float Voltage - SMR Default
SMR Float
54.5V
*Cannot be adjusted here
Equalise Voltage - SMR Default
SMR Equalise
56.5V
*Cannot be adjusted here
ENTER
SMR voltage above which alarm flagged
SMR V high Alarm
57.0V
Modify Value up/down
ENTER to accept
ENTER
SMR voltage below which alarm flagged
SMR V low Alarm
48.0V
Modify Value up/down
ENTER to accept
ENTER
SMR high voltage shutdown
SMR HVSD
58.5V
Modify Value up/down
ENTER to accept
ENTER
SMR current limit
SMR I Limit
30A
Modify Value up/down
ENTER to accept
Resets any latched SMR alarm
Reset SMR Fault
Press ENTER
Home Screen
Home Screen
25.2A 54.3V
FL
LOG Button
ENTER
Most recent logged Alarm/Event
LOG 1
AC Fail
10/10/2005
17:32:56
ENTER
Additional screens if more events logged
(
)
:
:
:
:
DEC
ENTER
100th most recent logged event
LOG 100
Battery Sw Open
3/1/2005
02:05:14
Older events are erased
INC
DEC
(
)
DEC to Clear
LOG Entries
LOG
No Entries