Installation
Sageon II Bulk Product Manual
PM990-5201-00, Issue 6
3-10
3.11
AC OPTION BOX (LIST 41 & 61)
Lists 41 and 61 come pre-wired with individual AC Breaker, Battery Distribution Module (BDM), and Multi-Input Battery
Temperature Board. The AC breakers provide protection to the rectifier. The battery distribution module allow for battery
current monitoring via current transducers (opt). Up to four battery strings can be monitored. The BDM can also monitor up
to four external battery circuit breakers. The battery temperature board allows monitoring with optional temperature sensors.
All boards are factory wired and allow for easy customer connection access.
Figure 3-14 AC Option Box Rear View (screens removed for clarity)
3.12
ADDING AUXILIARY EXPANSION MODULES
Modules such as the Sageon Battery Monitor, AC monitor, and site monitor are daisy chained from the unused ribbon cable
connection provided on the Auxiliary programmable relay board. All of these expansion modules are required to be mounted
external to the Power Module, and a single 16-way ribbon cable connected to the available box-header.
For more detailed installation information for each of these modules, refer to the Sageon Battery Monitor Operation Manual
(PM990-4209-00) and the Sageon Site Monitor Application Note (AN103-4012-00).
The MAC ID can have format
00-20-4A-24-BB-42 or
00:20:4A:24:BB:52.