Micro
ARE-M Series 24V Chargers, Single Phase
Setup and Operation
PM990-1070-24, Issue 12
4-16
3.
At the
Power On Defaults
screen, press SEL to return to the factory defaults or press ESC to return
to the
System Setpoints
screen.
4.3.4.7
Factory Calibration
Factory Calibration is intended for use by factory personnel and is not field accessible. Contact
UNIPOWER Service for additional information.
4.3.4.8
Field Calibrations
The only user adjustment on the Interface Board (A1) is load share adjustment R63. No other settings are
field adjustable. All other field adjustments are described previously in this chapter.
4.3.4.9
Field Connection and Calibration of Loadshare
Load sharing allows two or more ARE Series and ARE-M Series units connected in parallel to share the
load in proportion to their ratings. The power supplies will share the load within 5% of the rating of the
largest unit between 10% and 100% of their ratings. The load sharing is connected through the no charge
alarm, which disconnects the load sharing should one charger be shut off.
Connections
For load sharing, connect all units which are to share the load to the system bus using equal lengths of
properly sized cables. Connect #18 AWG insulated wire from TB2-3 or 4 (LOADSHARE) on the
Interface Board (A1) of charger A to TB2-3 or 4 (LOADSHARE) on the Interface Board (A1) of charger
B.
Adjustment
The loadshare is set at the factory and normally does not require any adjustment. If adjustment is needed,
follow the procedure below.
A.
For each unit, turn on only one unit at a time and adjust the output voltage to the desired level.
B.
Connect a digital voltmeter positive lead to the power supply positive output and the negative
lead to TB2-3 or 4 (LOADSHARE) on the Interface Board (A1). No other connections should be
made to these terminals on the interface board.
C.
Adjust potentiometer R63 on the interface board for 5.0VDC at zero output current.
For Two Power Supplies
A.
Turn on both units. Verify Load sharing is enabled on both units. (See 4.3.4.4)
B.
Add some load to the system and adjust R63 on the unit with lower output current to match the
output current of the other unit. For best results, the load should be between 50% and 100% of
the combined rating of the two units.
For More Than Two Power Supplies
Start by adjusting two of the units then add the rest of the units one at a time, adjusting R63 on each
added unit until all units are sharing the load.