ARE-M Series 24V Chargers, Single Phase
Introduction
PM990-1070-24, Issue 12
1-6
AC Breaker Interrupt Current ................. 2,000A @ 240V (5,000A @ 125V or with a 125A series fuse)
AC Breaker Interrupt High Capacity ...... 10,000A
Heat Dissipation...................................... 660 BTU/Hour
ARE-M02450
DC Output Voltage and Current ............. 26.4V @ 50A
Ripple
On Battery ......................................... NA
Off Battery ......................................... 30 mV rms
No. Cells, L-A......................................... 12
Recommended DC Cable ....................... 4 AWG (21.1 mm
2
)
Terminal Block Capacity ........................ 14-2/0 AWG (2.1 to 67.4 mm
2
)
DC Circuit Breaker ................................. 70A
AC Input Voltage and Current ................ 120V @ 16A, Single Phase
208V @ 9A, Single Phase
240V @ 8A, Single Phase
480V @ 4A, Single Phase
AC Frequency ......................................... 57-63 Hz
AC Breaker Interrupt Current ................. 2,000A @ 240V (5,000A @ 125V or with a 125A series fuse)
5,000A @ 480V
AC Breaker Interrupt High Capacity ...... 10,000A except 18,000 @ 480Vac
Heat Dissipation...................................... 1150 BTU/Hour
ARE-M024100
DC Output Voltage and Current ............. 26.4V @ 100A
Ripple
On Battery ......................................... NA
Off Battery ......................................... 30 mV rms
No. Cells, L-A......................................... 12
Recommended DC Cable ....................... 1 AWG (42.4 mm
2
)
Terminal Block Capacity ........................ 14-2/0 AWG (2.1 to 67.4 mm
2
)
DC Circuit Breaker ................................. 125A
AC Input Voltage and Current ................ 120V @ 33A, Single Phase
208V @ 19A, Single Phase
240V @ 16A, Single Phase
480V @ 8A, Single Phase
AC Frequency ......................................... 57-63 Hz
AC Breaker Interrupt Current ................. 2,000A @ 240V (5,000A @ 125V or with a 125A series fuse)
5,000A @ 480V
AC Breaker Interrupt High Capacity ...... 10,000A except 18,000 @ 480Vac
Heat Dissipation...................................... 2390 BTU/Hour
*Battery
: A fully charged battery that has an ampere-hour capacity numerically equal to four times the
rated output current of the charger.