![Unipower ARE-M02406 Скачать руководство пользователя страница 13](http://html1.mh-extra.com/html/unipower/are-m02406/are-m02406_product-manual_3893790013.webp)
Micro
ARE-M Series 24V Chargers, Single Phase
Introduction
PM990-1070-24, Issue 12
1-5
1.3.2 Electrical
Model Specific and Related Specifications
Refer to the equipment nameplate for the model number of the
Micro
ARE-M at hand.
ARE-M02406
DC Output Voltage and Current ............. 26.4V@ 6A
Ripple
On Battery ......................................... NA
Off Battery ......................................... 30 mV rms
No. Cells, L-A......................................... 12
Recommended DC Cable ....................... 14 AWG (2.1 mm
2
)
Terminal Block Capacity ........................ 24-12 AWG (.21-5.3 mm
2
)
DC Circuit Breaker ................................. 10A
AC Input Voltage and Current ................ 120V @ 2A, Single Phase
208V @ 1.1A, Single Phase
240V @ 1A, Single Phase
AC Frequency ......................................... 57-63 Hz
AC Breaker Interrupt Current ................. 2,000A @ 240V (5,000A @ 125V or with a 125A series fuse)
AC Breaker Interrupt High Capacity ...... 10,000A
Heat Dissipation...................................... 200 BTU/Hour
ARE-M02412
DC Output Voltage and Current ............. 26.4V @ 12A
Ripple
On Battery ......................................... NA
Off Battery ......................................... 30 mV rms
No. Cells, L-A......................................... 12
Recommended DC Cable ....................... 12 AWG (3.3 mm
2
)
Terminal Block Capacity ........................ 24-12 AWG (.21-3.3 mm
2
)
DC Circuit Breaker ................................. 20A
AC Input Voltage and Current ................ 120V @ 4A, Single Phase
208V @ 2.3A, Single Phase
240V @ 2A, Single Phase
AC Frequency ......................................... 57-63 Hz
AC Breaker Interrupt Current ................. 2,000A @ 240V (5,000A @ 125V or with a 125A series fuse)
AC Breaker Interrupt High Capacity ...... 10,000A
Heat Dissipation...................................... 440 BTU/Hour
ARE-M02425
DC Output Voltage and Current ............. 26.4V @ 25A
Ripple
On Battery ......................................... NA
Off Battery ......................................... 30 mV rms
No. Cells, L-A......................................... 12
Recommended DC Cable ....................... 8 AWG (8.4 mm
2
)
Terminal Block Capacity ........................ 14 - 10 AWG (2.1 to 5.3 mm
2
)
DC Circuit Breaker ................................. 35A
AC Input Voltage and Current ................ 120V @ 8.3A, Single Phase
208V @ 4.7A, Single Phase
240V @ 4.1A, Single Phase
AC Frequency ......................................... 57-63 Hz