![Unipower ARE-M02406 Скачать руководство пользователя страница 49](http://html1.mh-extra.com/html/unipower/are-m02406/are-m02406_product-manual_3893790049.webp)
Micro
ARE-M Series 24V Chargers, Single Phase
Setup and Operation
PM990-1070-24, Issue 12
4-14
3.
At the
Auto-Equalize
setup screen, press SEL. The
AC Fail Equalize after
screen will appear.
4.
Press SEL. The equals sign will flash. Press DN until DISABLED appears. Press SEL.
5.
Press ESC to return to the
Auto-Equalize
screen. Either press UP or DN to move to another
Setup
Select Screen
or press ESC until the
Home
screen appears.
To disable Periodic Equalize:
1.
At the
Home
screen, press UP or DN until CHARGER SETUP appears. Press SEL.
2.
At the
System Setpoints
screen
,
press UP or DN until the
Auto-Equalize
screen appears.
3.
At the
Auto-Equalize
setup screen, press SEL. Press UP or DN until the
Periodic Equalize
screen
appears.
4.
Press SEL. The equals sign will flash. Press DN until DISABLED appears. Press SEL.
5.
Press ESC to return to the
Auto-Equalize
screen. Either press UP or DN to move to another
Setup
Select Screen
or Press ESC until the
Home
screen appears.
4.3.4.4
Load Share
There are two Load Share modes: Load Share Standard and Load Share Legacy. Select Standard when
two or more
Micro
ARE-Ms, the chargers described in this manual, are to share a load. Legacy is used
when a
Micro
ARE-M is to share a load with an earlier model ARE.
To enable Load Share:
1.
From the
Home
screen, press UP or DN until CHARGER SETUP appears. Press SEL.
2.
From the
Load Share
screen press SEL. The
Load Share Disabled
screen will appear.
3.
Press UP to display the Load Share statuses: press UP for Load Share Standard; press UP again to
display Load Share Legacy.
4.
Press SEL to store the new status.
5.
Press ESC to return to the
Load Share
screen. Either press UP or DN to move to another
Setup Select
Screen
or Press ESC until the
Home
screen appears.
To disable Load Share:
1.
At the
Load Share
screen press SEL. The
Load Share Enabled
screen will appear.
2.
Press DN until DISABLED appears.
3.
Press SEL to store the new status and go to the
Load Share
screen. Either press UP or DN to move to
another
Setup Select Screen
or Press ESC until the
Home
screen appears.
Note: Refer to section 4.3.4.9 for additional Load Share setup information.
4.3.4.5
Password
Password protection allows only authorized personnel to change parameter values in the
Operating
Mode
menu (Figure 4-3) and
Charger Setup
menu (Figure 4-4). While password protection is disabled
by default, enabling password protection is recommended.
Anyone with access to the charger front panel can view alarms and parameter values in the
Active
Alarms
screen and the
Charger Status
menu (Figure 4-2). Password protection is not needed since these
are read-only displays.