CIB UNIGAS - M039177CA
21
Electrical wiring diagram for burners provided with printed circuit (standard configuration).
As far as connections, refer to the terminal block showed on Fig. 23.
1
Connect the signal conductors from the boiler to the burner, as for the next elements (Fig. 24 - Fig. 26):
ST: thermostat/pressure switch series
TAB: High/low flame thermostat
2
Connect the signal conductors from the burner to the boiler, as for the next elements (Fig. 24 - Fig. 26)
LB: Burner’s lockout signalling LED
LSPG: Gas proving system’ lockout signalling LED
3
In case of modulating burners, the 5, 6 and 7 terminals, on the MA teminal block, are already connected to the regulating modula-
tor (mod. RWF40). A 4-pole plug coming out from the electrical panel is provided for the temperature and pressure probes connec-
tions (see Fig. 25).
Note: the regulating modulator is provided according to the ordered probe
Fig. 23: Terminal board for connections on printed circuit
Fig. 24: Progressive burners
Fig. 25: Probes connection
Fig. 26: Fully modulating burners
RWF40 >>>
Содержание TP512A
Страница 43: ...CIB UNIGAS M039177CA 43 Wiring diagram 21 001 2 Progressive burners ...
Страница 44: ...CIB UNIGAS M039177CA 44 Wiring diagram 21 001 2 Fully modulating burners ...
Страница 46: ...CIB UNIGAS M039177CA 46 ...
Страница 47: ...CIB UNIGAS M039177CA 47 ...
Страница 48: ...CIB UNIGAS M039177CA 48 ...
Страница 49: ...CIB UNIGAS M039177CA 49 WIRING DIAGRAM Cod 09 315 1 Burners type TP525A Mod M MD x xx x 1 xx ...
Страница 50: ...CIB UNIGAS M039177CA 50 ...
Страница 51: ...CIB UNIGAS M039177CA 51 ...
Страница 52: ...CIB UNIGAS M039177CA 52 ...
Страница 55: ...CIB UNIGAS M039177CA 55 ...
Страница 56: ......