PART III: OPERATION
35
to the maximum output.
Manual mode
To by-pass the thermal protection or not to let the buner operate in high flame stage (maximum output) after ignition, the manual mode
is provided.
To choose the manual mode (Manual Operation), use the SELECT arrow keys
Items to be set are the following:
SetLoad
: to set the required load percentage
set the required percentage and confirm by pressing ENTER; press ESC to exit.
choose “Autom/Manual/Off
three modes are provided:
Automatic
: automatic operation
Burner on
: manual operation
Burner off:
burner in stand-by
If the BurnerOn mode is choosen,the burner does not follow the modulator and probe settings, but operates at the set load.
For further details, see the LMV5x annexed manuals.
OperationalStat
Operation
ManualOperation
Params & Display
SetLoad
Autom/Manual/Off
SetLoad
Curr::
0.0%
New:
20.0%
SetLoad
Autom/Manual/Off
Autom/Manual/Off
Curr::
Automatic
New:
Burner On
Caution
: if BurnerOff mode is selected, the burner stays in stand-by.
Caution
: in the BurnerOn mode, the safety thresholds are set by the Technical Service.
Содержание HRX2060
Страница 39: ...PART III OPERATION 39 Pump flow rate Nozzle flow rate...
Страница 49: ...Siemens LMV5x Service Manual M12920CC rev 2 1 08 2017...
Страница 56: ...8...
Страница 57: ...9 1 4 1 Servomotor wiring example 1 4 2 Bus cable wiring on LMV5x and AZL doors 1 4 3 EARTH connection example...
Страница 60: ...12 2 2 LMV5x program structure...
Страница 87: ...39...
Страница 94: ......
Страница 95: ......
Страница 96: ...Note Specifications and data subject to change Errors and omissions excepted...
Страница 98: ...Annex1 Example for motor cable...
Страница 99: ......
Страница 100: ...Annex 2 Example for sensor cable...
Страница 101: ......
Страница 102: ......
Страница 106: ......