Termi- nal
group
Connection symbol
Inpu
t
Out
pu
t
Description of connection termi- nals
Electrical rating
X10-01
PIN4
x
Neutral conductor (N)
AC 230 V +10 % / -15 %, 50...60 Hz,
max 1 mA
PIN3
x
Power
signal
transformer
PIN2
x
AC power signal GO
AC 12 V +10 % / -15 %, 50...60 Hz,
max 1.2 mA
PIN1 x
AC power signal fan motor (G)
X10-02
PIN6
x
QRI... (IR detector) / QRA7... signal
voltage
Umax DC 5 V
PIN5
x
Protective
earth
(PE)
PIN4
x
Neutral
conductor
(N)
PIN3
x
Power signal
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 500 mA
PIN2
x
QRI... (IR detector) / QRA7... power
supply
DC 14 / 21 VC Imax 100 mA
PIN1
x
QRB... signal voltage
Max. DC 8 V
X10-03
PIN1
x
Ionization probe (ION) (alternati- vely
QRA2…/ QRA4.U/QRA10…, refer to
section
Description of inputs and out-
puts
)
Umax (X3-04-PINS) Imax. 0.5 mA
X50
PIN6
x Reference ground (PELV)
PIN5
x
Communication signal (CANL)
DC U <5 V, Rw = 120 Ù, level to ISO-DIS
11898
PIN4
x
Communication
signal
(CANH)
PIN3
x
AC power supply for actuators / display
and operating unit AZL5...
AC 12 V +10 % / -15 %, 50...60 Hz,
Fuse max. 4 A
PIN2
x
AC power supply for actuators / display
and operating unit AZL5...
PIN1
x
Shield connec-
tion
(functional earth)
X51
PIN6
x Reference ground (PELV)
PIN5
x
Communication signal (CANL)
DC U <5 V, Rw = 120 Ù, level to ISO-DIS
11898
PIN4
x
Communication
signal
(CANH)
PIN3
x
AC power supply for actuators / display
and operating unit AZL5...
AC 12 V +10 % / -15 %, 50...60 Hz,
Fuse max. 4 A
PIN2
x
AC power supply for actuators / display
and operating unit AZL5...
PIN1
x
Shield connec-
tion
(functional earth)
Содержание HRX2060
Страница 39: ...PART III OPERATION 39 Pump flow rate Nozzle flow rate...
Страница 49: ...Siemens LMV5x Service Manual M12920CC rev 2 1 08 2017...
Страница 56: ...8...
Страница 57: ...9 1 4 1 Servomotor wiring example 1 4 2 Bus cable wiring on LMV5x and AZL doors 1 4 3 EARTH connection example...
Страница 60: ...12 2 2 LMV5x program structure...
Страница 87: ...39...
Страница 94: ......
Страница 95: ......
Страница 96: ...Note Specifications and data subject to change Errors and omissions excepted...
Страница 98: ...Annex1 Example for motor cable...
Страница 99: ......
Страница 100: ...Annex 2 Example for sensor cable...
Страница 101: ......
Страница 102: ......
Страница 106: ......