PART II: INSTALLATION
24
Suntec T
"Note: pump with “C” rotation.
Suntec TV Pressure governor
Oil viscosity
3 ÷ 75 cSt
Oil temperature
0 ÷ 150 °C
Min. suction pressure
- 0.45 bar to avoid gasing
Max. suction pressure
5 bar
Rotation speed
3600 rpm max.
Pump Suntec AS47 A
Viscosity
2 ÷ 12 mm²/s (cSt)
Fuel temperature
0 ÷ 60 °C
Maximum inlet pressure
2 bar
Minimum inlet pressure
- 0.45 bar to avoid gasing
Maximum Return pressure
2 bar
Maximum speed
3600 rpm
Key
1
Inlet G3/4
2
Pressure gauge port G1/4
3
Vacuum gauge port to measure the inlet vacuum G1/4
4
To pressure adjusting valve G3/4
Key
1. Pressure regulator
2. Pressure gauge port
3. Vacuum gauge port
4. Solenoid valve
5. Delivery to nozzle
7. Inlet
8. Return
Pressure adjustment
Remove cap-nut 1 and the gasket 2, unscrew the lock nut 4. To increase
pressure, twist adjusting screw 3 clockwise.
To decrease the pressure, twist screw counterclockwise. Tight the lock
nut 4, refit the gasket 2 and the cap nut 1.
Key
1 Cap nut
2 Gasket
3 Adjusting screw
4 Lock nut
5 Gasket
Speed Sensor
AGG 5.310
is a speed sensor kit used to monitor the speed of a motor. This kit is used to mount the speed sensor directly on the motor casing.
Содержание HRX2060
Страница 39: ...PART III OPERATION 39 Pump flow rate Nozzle flow rate...
Страница 49: ...Siemens LMV5x Service Manual M12920CC rev 2 1 08 2017...
Страница 56: ...8...
Страница 57: ...9 1 4 1 Servomotor wiring example 1 4 2 Bus cable wiring on LMV5x and AZL doors 1 4 3 EARTH connection example...
Страница 60: ...12 2 2 LMV5x program structure...
Страница 87: ...39...
Страница 94: ......
Страница 95: ......
Страница 96: ...Note Specifications and data subject to change Errors and omissions excepted...
Страница 98: ...Annex1 Example for motor cable...
Страница 99: ......
Страница 100: ...Annex 2 Example for sensor cable...
Страница 101: ......
Страница 102: ......
Страница 106: ......