FORCE 50
REV. 2.2 2021-02-04
4-4
UNIFIRE FORCE 50 Robotic Nozzle
Installation and setup manual
MECHANICAL INSTALLATION
50 meters
35 meters
Installation hanging from the ceiling
Is recommended for fully automatic systems. It usually will provide better reach, the stream is less obstructed by objects on
the floor. Up to 40 m reach provide a full 80 meter Ø cover. It is however difficult to control with a manual Joystick, because
the geometry is rotated 90°, with the Nozzle facing straight down in default position.
Installation on the wall
Usually provides easier access, thus it makes installation easier. The cover is limited to only 180° horizontal reach.
An area of up to 40 m radius is protected. Installing on a wall provides a geometry suited for manual Joystick control.
35 meters
50 meters