UNIFIRE FORCE 50 Robotic Nozzle
Installation and setup manual
PLANNING
System Limitations
The system designer shall take into account the building
construction or vehicle requirements, location, hydraulic
design, coverage area, and number of systems required. If
the limitations in these areas are not maintained, the system
may not operate correctly.
Building Construction
•
Water demand:
Evaluate the FORCE 50 water system
demand as an independent addition to the existing
building water supply. Conduct a hydraulic analysis to
ensure that it does not affect the building’s existing water
system design criteria. It is possible to achieve this without
significant system supply modifications. However, the
system may require increased pump sizes, storage tank
capacity, and pipe sizes.
Determining a Location
Contact your local technical support team for assistance in
determining the optimal location of the system components.
Water connection
The FORCE 50 is normally delivered with a DN50/PN16
stainless steel flange.
Options include 2” male BSP, JIS and ANSI flanges, and
customer specific brackets.
Please discuss the connection with your sales represen-
tative and please specify the requested connection when
ordering.