32
Installation instructions
3.19 - PROGRAMMING
HEATING CONTROLLERS WITH
BOILERS IN CASCADE
For that which concerns adjustment and programming of the
heating modules, see the instruction booklets attached to the
individual heating controller.
The following are the default parameters which “cannot be
modified”.
As far as parameters which can be programmed by the user
according to his requirements, see the system manager
instruction book.
Default
Individual values
Value range
Description
INSTALLATION
0000 - 9999
CODE NUMBER
ENTRY
0000 - 9999
CODE NUMBER (adjustment)
0000
(00), 01 - 015
BUS ID
11111
01
(00), 01 - 016
BUS ID
22222
02
00,01 (OFF/ON)
AF SUPPLY
01 (ON)
PARAMETERS PROGRAMMABLE BY TECHNICIAN AND PROTECTED BY ACCESS CODE FOR
HEATING CONTROLLER type E8.5064
00, 01 (OFF / ON)
TEMPERATURE MASTER
30 °C - 110 °C
MAX-T HS1 MAX T-HEADER
10 °C - 80 °C
MIN-T HS1 MIN T-HEADER
01 (ON)
85 °C
10 °C
0,01
BUS CONNECTION
01
00,01 (OFF/ON)
BUS SUPPLY
01 (ON)
2K - 20K
HYSTERESIS
00 - 30 min
HYSTERESIS TIME
00, 01, 02
MINIMUM LIMIT
5
00 min
00
30 °C - 110 °C
MAX-T HS2
85 °C
......, 01 - 08
BOILER BUS ID
----
10 °C - 80 °C
MIN-T HS2
10 °C
0 - 11
VOLTAGE CURVE
11
0,00-10,00V
CURVE 11-U2
0V
0,00-10,00V
CURVE 11-U2
10V
00 - 120 °C
CURVE 11-T1
0 °C
00 - 120 °C
CURVE 11-T2
100 °C
0,00-10,00V
CURVE 11-UA
0V
10 °C - 85 °C
T-WARM-UP
10
DISPLAY ONLY
BOILER DETECTED
00 - 1000kW
OUTPUT LEVEL
* see note
00,01 (OFF/ON)
NEW CONFIGURATION
00 - 100
MINIMUM MODULATION CASCADE
00
00 - 08
DHW LEVELS
00
(K)
CONTROL VARIANCE
DISPLAY
0 - 100%
NOMINAL OUTPUT INDEX
DISPLAY
(-99) - 0 - (99)
SWITCH VALUE
DISPLAY
REMAINING (min)
BLOCK TIME
DISPLAY
50 - 110°C
MAXIMUM BOILER TEMPERATURE
85
20 - 500K
BOILER DYNAMICS UPWARD
30K