51
Instructions for the installer
It avoids system shutdown in case the main boiler
plant’s system management is out of use.
A)
In position I the plant will operate when requested
at “CONSTANT SETPOINT”: 70°C – Max heat
output 50%
B)
Enables burner reset in case of lock-out
C)
TLG General Limit Thermostat: when it acts, it cuts the
power supply to the boiler, the warning lamp D lights.
To reset, remove the cap and push the reset button.
D)
Warning lamp of the thermostatic lockout of TLG
E)
Change-over
0
=
Emergency is active
I
=
Series connection (the cascade is managed
by the BCM)
II
=
Parallel connection (the cascade is managed
by the E8)
F)
Relay of the condensate level sensor: when the led is
On it means every thing is OK;
when the led is Off it means that the condensate level
sensor has cut the power supply to the boiler, and the
boiler stays Off till the level of the condensate
decreases under a certain level.
Note: The switches are positioned under
the front panel.
Note: The emergency function enables the
boiler’s burners to fire only at 50% and at
50°C in system return. All the system’s
heating loads, including the header pump,
must be controlled manually.
I
II
A
B
C
D
E
F
3.29 - EMERGENCY FUNCTIONS
Yellow LED = Blinking
(communication between BMM and BCM)
OK
Green LED = ON (Pump enabled)
Red LED = ON (Failure code detected)