19
Instructions for the installer
3.6 -
BOILER CONNECTION
The boiler Modulex leaves the factory predisposed for the
hydraulic and gas connection on the back side of the boiler.
The smoke outlet is placed on the back side of the boiler
for MODULEX 440;
it's placed on the R.H. side of the boiler for MODULEX 550 -
660 - 770 - 900.
For the smoke chamber fixing, use the screws and gaskets
included into the instruction bag, and a cross screwdriver at
least 300 mm of length.
When the appliance is installed on existing systems, ensure
yourself that:
- The flue outlet pipe is suitable for condensing boilers, for
the temperature of the products of combustion, calculated
and manufactured according to the regulations in force. It
must be installed as much as possible in a straight line,
tested for soundness, insulated and must not have any
occlusions or restrictions.
- The flue outlet pipe has a connection for the discharge of
condensate.
- The boiler room has a suitable outlet for the discharge of
condensate produce by the boiler.
- The electrical system has been fitted in compliance to the
specific norms and the work has been carried out by a
competent person.
- The circulation pump’s output, the head and flow direction
are suitable.
- The gas feeding supply pipe and the eventual tank are
constructed according to the regulations in force.
- The expansion vessels assure the total absorption of the
dilatation of the fluid contained in the system.
- The system has been cleaned of impurities and lime scale.
When a Modulex boiler is installed onto an existing
heating system:
In case the replacement of an existing boiler in
an old system can be programmed, it
is
necessary to thoroughly clean out the system
with a basic solution. The system must be
cleaned 4 weeks before the substitution, with
the system firing at a temperature of 35°C to
40°C.
WARNING!
If it is noticed that a new Modulex has replaced, in an old
system the existing boiler without having first performed what
said in the previous paragraph, Do not wash now the system,
as residual products, present in the circuit, could lead to sy-
stem gathering in the boiler body, causing damage. UNICAL
recommends contacting a specialised company for water tre-
atment.
Instead, if installing a Modulex boiler in a new system,
it is
still recommended to thoroughly clean out the system with an
adequate product and fit a Y filter with two isolating valves
onthe boiler’s return pipe, so that, when necessary, it can be
cleaned. This filter will protect the boiler from the dirt coming
from the heating system.
When sizing pumps, it is necessary to take into consideration
the pressure losses which occurin the primary circuit.
3.5 -
INSTALLATION ON EXISTING HEATING SYSTEMS