48
Instructions for the installer
3.28 -
BURNER ADJUSTMENT
WARNING!
All the instructions indicated below are for the
exclusive use of qualified UNICAL service
technicians or installers.
A) Max output adjustment
Remove the cap of the combustion gases sampling point
-
Connect a suitable C0
2
gas analyser to the sampling
point in the flue inlet/outlet terminal.
-
Force the desired burner working at nominal output
(CASCADE MAN 100%)
-
Check that the C0
2
values are within the values
indicated in the table “Burner pressures”
-
If necessary correct the value by turning the adjustment
screw “A” in a CLOCKWISE direction to decrease the
value and in an ANTICLOCKWISE direction in order to
increase it.
Follow this procedure also for the other burners
B) REGOLAZIONE ALLA POTENZA MINIMA
-
Force the desired burner working at minimum output
(CASCADE MAN 10%)
-
Check that the C0
2
values are within the values
indicated in the table “Burner pressures”
-
If necessary correct the value by turning the adjustment
screw “B” in a CLOCKWISE direction to increase the value
and in an ANTICLOCKWISE direction in order to decrea
se it.
Follow this procedure also for the other burners
All the boilers are supplied already calibrated
and tested. If it is necessary to change the
calibration due to gas conversion or adaptation
to the mains supply system, the gas valve must
be re-calibrated.
MAXIMUM OUTPUT
ADJUSTMENT SCREW
MINIMUM OUTPUT
ADJUSTMENT
SCREW
Содержание SuperModulex 440