27
Instructions for the installer
3.17 - CONDENSATE DRAIN
Avoid the condensate stagnation inside the combustion
products evacuation system, (for this reason the evacuation
duct must have an inclination toward the drain of at least 30
mm/m (3/8 in. / ft) except the liquid column, inside the
condensate siphon, which needs to be filled with water after
installation: its minimum height, when all the fans are in oper-
ation, must be at least 25 mm (1 in.).
In order to avoid ice formation while the boiler is operating,
which can cause the stop of the boiler, the whole condensate
evacuation system has to be well insulated. It is forbidden to
evacuate the condensate through a gutter: risk of ice forming
and corrosion.
The condensate, before being evacuated to the sewer, has to
be neutralized, neutralisation which can be obtained by
mixing the drain water coming from washing maschines,
dish washing maschines, etc., which normally have a ba-
sic pH.
The connection to the sewer will be through a visible drain.
Given the high acidity degree (pH 3 to 5) only plastic ma-
terial can be used for the condensate evacuation pipes.
Moreover it must be dimensioned and constructed so as
to allow the correct out-flow of drains, preventing any bot-
tleneck and any leakage.
BACK SIDE
The outlet of the condensate drain pipe will be on the same
side of the smoke chamber, passing below the smoke cham-
ber.
Before commissioning the boiler fill the con-
densate siphon with water, from the dedica-
ted filling-up plug.
*
Min. height of the condensate column, with all fans
operating at max. speed, requested by the EN stan-
dards.
** Min. height of the condensate column, with all fans opera-
ting at max. speed. In the case it is not possible to create a
100 mm basement, install the boiler on the floor and fore-
see a min. 100 mm well to lodge the siphon.
150
150
BOILER
HOUSE
FLOOR
INITIAL SIPHON
FILLING-UP PLUG
The upper part of the drain
pipe shall not be higher
than the tray bottom.