26
Instructions for the installer
30.000
50.000
100.000
150.000
200.000
250
300
400
500
600
440
550
66
0 - 900
power supply
over > 340 kW
125
150
200
250
300
125
150
200
250
300
200
250
250
300
300
1.000
1.000
1.500
1.500
1.800
300
300
300
400
400
150
150
200
300
300
1.650
1.700
2.250
2.500
2.800
200
200
200
200
200
3
.15 - BOILER FREEZE PROTECTION
Should the flow temperature (measured at global flow tempera-
ture NTC) decrease under 7°C, the system pump is set up. Shoul
temperature decrease to under 3°C, all modules will start at min.
output until the return temperature reaches 10°C.
Such protection device is exclusively for the boiler. For the pro-
tection of the system, a second freeze protection thermostat is
necessary to switch on the heating system pump.
To protect the C.H. system from freezing when boiler is not in
operation during cold season, it is necessary to add to the C.H.
system water an anti freezing solution.
NB: The antifreezing solution must be compatible with the
materials present in the system, and mainly with the
aluminum.
3.16 -
MIXING HEADER
AND PLATE HEAT EXCHANGER
D
1/2’’
KV
KR
HR
g
a
b
c
h
e
HV
1/2’’
1/2’’
1/2’’
g
CH FLOW
CH RETURN
F
I
L
T
E
R
CH FLOW
CH RETURN
Boiler
Circuit
Heating
System
Circuit
In order to ensure correct boiler operation it is necessary to
use a mixing header which guarantees:
-
the separation and collection of circuit dirt
-
optimal air venting
-
hydraulic de-coupling of the two hydraulic circulation
circuits
-
balancing of the circuits
M
M
R
R
Boiler
Circuit
Heating
System
Circuit
The plate heat exchanger, conveniently dimensioned, has the
advantage to keep hydraulically the two circuits (primary and
secondary), thus allowing the installation of the MODULEX
boiler also in industrial processes.
WARNING
AFTER A LONG INOPERATION PERIOD OF THE
BOILER, IN CASE THE BOILER TEMPERATURE
IS BELOW 3°C, ABSOLUTELY DO NOT TRY TO
START THE BOILER.
THIS CAN BE ALLOWED ONLY IF YOU ARE SURE THAT AN
ANTIFREEZE SOLUTION HAS BEEN ADDED, IN THE PROPER
PERCENTAGE, TO THE C.H. WATER.
See the Unical catalogue and the price list to
identify the most convenient mixing header and
primary circuit.
TABLE FOR THE RECOMMENDED DIMENSION OF THE
HYDRAULIC COMPENSATOR
Содержание SuperModulex 440
Страница 2: ...2 ...
Страница 17: ...17 Instructions for the installer 1 2 3 4 A B PALLET REMOVAL BOILER UNLOADING AND PACKAGE REMOVAL ...
Страница 59: ......