12
Technical features and dimensions
2.3 -
PERFORMANCE DATA
B
BOILER TYPE
SUPERMODULEX
Appliance category
II
2H3P
Nominal Heat Input on P.C.I.
Qn
kW
Minimum Heat Input on P.C.I.
Qmin
kW
Nominal Output (Tr 60 / Tm 80 °C)
Pn
kW
Minimum Output (Tr 60 / Tm 80 °C)
Pn min
kW
Nominal Output (Tr 30 / Tm 50 °C)
Pcond
kW
Minimum Output (Tr 30 / Tm 50 °C)
Pcond min
kW
Efficiency at max. output (Tr 60 / Tm 80°C)
%
Efficiency at min. output (Tr 60 / Tm 80°C)
%
Efficiency at max. output (Tr 30 / Tm 50°C)
%
Efficiency at min. output (Tr 30 / Tm 50°C)
%
Efficiency Class acc. to Directive 92/42 CEE
Combustion efficiency at nominal load
%
Combustion efficiency at part load
%
Stand-by losses with burner in operation
%
Flue losses with burner with burner off
%
Flue losses with burner with burner in operation
%
Flue gas temperature tf-ta (max)
°C
Flue gas mass flow rate (max)
kg/h
Excess of air
λ
%
(**) CO
2
at min/max. output)
%
NO
X
(value according EN 297/A3 + EN 483)
mg/kWh
NO
X
class
Min. water flow rate in CH circuit (
Δ
T 20°C)
l/h
Minimum pressure in CH circuit
bar
Maximum pressure in CH circuit
bar
DHW specific flow rate
l
Gas Consumption
Natural gas G 20 (20 mbar) Qn
m
3
/h
Gas Consumption
Natural gas G 20 (20 mbar) Qmin
m
3
/h
Gas Consumption G25
(supply
pressure
25 mbar) Qn
m
3
/h
Gas Consumption G25
(supply
pressure
25 mbar) Qmin
m
3
/h
Gas Consumption
G31
(supply
pressure
37/50 mbar) Qn
kg/h
Gas Consumption G31
(supply
pressure
37/50 mbar) Qmin
kg/h
Max. available pressure at the chimney base
Pa
Condensate production max
kg/h
Emissions
CO with 0% of O
2
in the flue system
ppm
NO
x
with 0% of O
2
in the flue system
ppm
Sound level
dBA
Electrical Data
Voltage / Frequency
V/Hz
Fuse on main supply
A (F)
Max power absorbed
Insulation degree
IP
Standby Consumption
W
(*)
Room Temperature = 20°C
(**)See paragraph ‘’
INJECTORS – PRESSURES
’’
900
864
22
848,53
20,33
894,24
23,94
98,21
92,4
103,5
108,8
4
97,42
98,43
0,2
0,1
2,58
52
1399
24,25
-
47
5
36487
0,5
7
133
91,36
2,33
106,25
2,71
67,07
1,71
100
146,7
<95
<30
<49
230/50
4
1224
40
10
770
756
22
742,47
20,33
780,95
23,94
98,21
92,4
103,3
108,8
4
97,42
98,43
0,2
0,1
2,58
52
1224
24,25
-
47
5
31926
0,5
7
118
79,94
2,33
92,97
2,71
58,68
1,71
100
128,4
<95
<30
<49
230/50
4
1071
40
10
660
648
22
636,40
20,33
667,44
23,94
98,21
92,4
103,0
108,8
4
97,49
98,43
0,2
0,1
2,51
50,6
1049
24,25
-
47
5
27365
0,5
7
103
68,52
2,33
79,69
2,71
50,30
1,71
100
110
<95
<30
<49
230/50
4
918
40
10
550
540
22
530,33
20,33
554,04
23,94
98,21
92,4
102,6
108,8
4
97,47
98,43
0,2
0,1
2,53
51
874
24,25
-
47
5
22804
0,5
7
88
57,10
2,33
66,41
2,71
41,92
1,71
100
91,7
<95
<30
<49
230/50
4
765
40
10
440
432
22
424,27
20,33
442,37
23,94
98,21
92,4
102,4
108,8
4
97,42
98,43
0,2
0,1
2,58
52
699
24,25
-
47
5
18243
0,5
7
73
45,68
2,33
53,13
2,71
33,53
1,71
100
73,4
<95
<30
<49
230/50
4
612
40
10
The Technical data plate is placed under the
casing over the forehead stirrup.
Содержание SuperModulex 440
Страница 2: ...2 ...
Страница 17: ...17 Instructions for the installer 1 2 3 4 A B PALLET REMOVAL BOILER UNLOADING AND PACKAGE REMOVAL ...
Страница 59: ......