15
Instructions for the installer
3.9 - FURNACE DOOR, REGOLATION,
OPEINING, CLOSING.
IMPORTANT
- You must open the door when boiler is cold to prevent fiber
damage for the thermal shock.
- The fiber insulation door may have some cracks after a
short period of operation, this, however, does not reduce
the insulating capacity and not impede the duration.
3.9.1 - BOILERS INOXIA GJ 150 ÷ INOXIA GJ 350
For all these models, the hinge and fixing the door made
according to the scheme of fig. 10.
In these cases, the door is fitted with two rotation hinges on
the left side, and two locking pins on the right side, the two
hinges on the left side allow the closure
the door on this side, which is close by 4 screws (C).
It will have exactly the opposite, however, where the door will
open from left to right.
To perform the inversion of the rotation, just reverse the
hinges.
On the door of these models is possible the following
adjustment:
A)
adjustment in the axial direction
: You can tighten more or
less the screws “C”
.
fig. 10
- The fiber port is easily replaceable and is covered by 2
year warranty
.
3.9.2 - BOILERS INOXIA GJ 450 ÷ INOXIA GJ 1000
For all these models, the hinge and fixing the door
made according to the scheme of fig. 11.
In these cases, the door is fitted with four equal
hinges : the two on the left side, with pin
added, are normally used as hinges rotation
(from right to left), while the two on the right are
used as hinges closing; the door is then locked
with four screws.
It will have exactly the opposite, however, where
the door will open from left to right.
To perform the inversion of the rotation, just move
the pins on the opposite side.
On the door of these models are possible the following
adjustments:
A)
Vertical adjustment
: it is possible only with the inserting
of washers with suitable thickness under the hinge on which
rotates the door.
B)
Transversal Adjustment
: it is possible loose the hinges
fixed on the plate to the front of the boiler and moving them to
the side.
C)
Axial adjustment
: you can tighten more or less the nuts.
fig. 11
C
C
C
C
C
C
C
C
A
B
C
A
B
Содержание INOXIA GJ Series
Страница 1: ...INOXIA GJ INSTALLATION AND SERVICING MANUAL 00335290 1st edition 04 11...
Страница 21: ...21 Instructions for the installer fig 12 5 24 4 8 10 12 13 6 3 1 2 7 23 20 14 19 17 21 18 1 2 11 9 16 12 15...
Страница 54: ......