Instructions for the installer
For the connection of the flue pipe must be respected the
local and national regulations (see UNI-CIG 7129 4 point and
7131 point 5).
The INOXIA GJ boiler lends itself to different solutions for
connecting the chimney, it is possible, by pipe line or straight
curves, leaving the rear, left, right, or vertical
to take in the flue in a higher level.
It is recommended to isolate the connecting pipe to the
chimney to reduce heat loss and noise
In the stretch between the boiler and the chimney, it
must have suitable measuring points for the smokes
temperature and the analysis of combustion products.
WARNING: The temperature of the smoke produced from
burning are lower than the other non-condensing boilers
and have a content of high humidity
For this reason, the flue must be of a suitable material,
waterproof and resistant to the acid condense
.
It must also be sized to ensure adequate draft.
We recommend using only conducted drain
suitable for the type of fuel used.
Does not accept any responsibility
contractual and non- contractual of the
supplier for damages caused by errors during
the installation and the using and for the not
observances of the instructions given by the
manufacturer.
In the case of installation or replacement, replace
ALWAYS also the accessory exhaust fumes.
The chimney must comply with current standards.
3.7 -
FLUE CONNECTION
The discharge of condensate drain must be:
- designed to prevent the escape of the gas products or
combustion in the environment or sewer (siphon);
- Designed and realized in order to allow proper flow of the
liquid waste by preventing leaks;
- Installed in order to prevent freezing of the liquid that it
contains during the intended operating conditions;
- For example, mixed with domestic sewage (waste washing
machines, dishwasher, etc.). for the most basic pH in order
to form a buffer solution so that it can then enter sewage
system.
Should be avoid the stagnation of the condense in the system
exhaust of combustion products (which is why the flue must
have an inclination towards the discharge of at least 30 mm
/ m)
with the exception of any swing of liquid in the siphon
discharge system for the evacuation of the combustion
products (which must be filled after installation and the
minimum height with the boiler activated, it must be at least 25
mm-see Fig. 9).
You must not discharge the condensate through the rain
gutters, because the risk of ice and degradation materials
normally used in the creation of the rain gutter
themselves (see the local health regulations).
The connection to the discharge must be visible.
The level of condensate acidity (pH 3 to 5) as materials for
drain pipes must be used only plastics for (Special kits are
available with optional salt neutralizers of acid condensate
).
* Minimum Siphon of safety required by the standard
**Minimum ledge with working boiler at the maximum power.
In the event that you would or would not create a socket, the
boiler can be fitted at the floor level and create a deep pit at
least 100 mm to store the siphon
.
fig. 9
PAVIMENTO
DELLA C.T.
15
0
15
0
TAPPO DI RIEMPIMENTO
INIZIALE DEL SIFONE
La
di scarico
non dovrà trovarsi ad un livello superiore
al .
generatrice superiore del tubo
fondo della camera fumo
CAMERA FUMO
3.8 -
CONDENSATE DRAIN
SMOKE CHAMBER
PLINTH (H min 100 mm)
TO
CONDENSATION
DRAIN
SIPHON INITIAL
FILLING CAP
The upper generator of the drain pipe
must be higher at the bottom of the smoke
chamber.
BOILER
ROOM FLOOR