Operating and mounting manual 

         (translation) 

EVF 
 
 

 

 _______________________________________________________________________________________________________  

220.100.112-07 

Page 8 /13

 

Version: 12/2015 

TM 3926 

 

 

 

7.2 Troubleshooting 

plan 

Malfunction Possible 

causes 

Remedy 

No flow 

Valve does not open 

Switch on solenoid drive (800)  
Check operating voltage 

Working pressure too high 

Compare working pressure with the data 
on the rating plate 

Flange covers were not removed 

Remove flange covers 

Low flow rate 

Clogging in the pipework system 

Check pipework system 

Valve leaking at seat, 
no internal tightness 

Valve seat gasket (400) or valve seat 
(100) damaged by external particles 

See section 8 replace valve 

No external tightness  Gaskets damaged 

See section 8 replace valve 

Valve does not close  Connected voltage too high 

Check whether there is residual voltage, 
see section 4.1 

Flange fracture (valve/ 
pipework) 

Screws not tightened uniformly, mating 
flanges not aligned 

Align pipework. 
Install new valve 

 

NOTICE! 

Observe section 10.0 before all installation and repair work! 

 

Observe section 6.4 when putting the valve back into operation! 
 
 

8.0  Dismantling of the Valve

 

In addition to the general installation guidelines and the operation safety order, the following points 
must also be observed: 
 
 

DANGER!

 

 

Depressurised pipework system 

 Cooled 

medium 

 Emptied 

installation 

 

Vent pipework systems containing corrosive, inflammable, aggressive or toxic 
media 

 

Have dismantling work carried out only by qualified staff (see point 2.3) 

 

8.1 

Replacement of spare parts 

Shut down the valve as described in section 6.2. 

 
  

Fig. 1     40-EVF…NH.Ü..  (DN15 – DN25) ; 55-EVF…NH.Ü..  (DN15, DN25) 

 

 
De-installation of the limit switch mounting 

Switch limit switch (803) to zero-potential. Open limit switch housing (120). Loosen 
hexagon nut (901/2) and screw it off and remove it together with switch actuator 
(513) from the limit switch spindle (243). Loosen hexagon nut (901/3) and remove 
it. Take off the limit switch housing (120) with terminal box (716) from the limit 
switch connection piece (246). Remove connecting piece limit switch (246) from 
solenoid housing (800). 

 

 

Switch off and dismantle the solenoid drive (800) as described in the operating manual of the solenoid 
drive. 
 

DANGER! 
After continuous operation, the solenoid drive may be hot! Danger of burns! 

 
 
Replace the solenoid valve 

 

 
 

 

 

 

Содержание EVF Series

Страница 1: ...fety information for the use in explosion prone areas guideline 94 9 EC 3 0 Handling 3 1 Transport 3 2 Storage 3 3 Handling before mounting 4 0 Product Description 4 1 Function 4 2 Technical data 4 3...

Страница 2: ...of these operating instructions suppose the qualification of the user according to paragraph 2 3 qualified staff The operating staff must be trained in accordance with the operating instructions The...

Страница 3: ...TICE are used in this operating manual in case of notices concerning special dangers or for unusal information requiring a special marking DANGER means that in case of non observance there is danger t...

Страница 4: ...a pipe screws by means of tooth disc Otherwise the connection to the ground must be implemented by other measures e g cable links Control valves electrical and electrical mechanical drives as well as...

Страница 5: ...1 Fig in Fig 1 show the valve construction 4 1 Function On switching on of the solenoid drive 800 the solenoid core 207 is pulled against the upper part of housing 106 The pressure spring 503 is furth...

Страница 6: ...ion safety order and the qualified use of tools and protection equipment must be guaranteed The operating instructions for the valve must be observed during all work on or with the valve Failure to ob...

Страница 7: ...to the operating conditions UNI Ger te recommends an internal visual inspection once a year and an overhaul of the valve after 2 years or after the following number of switching cycles at the latest...

Страница 8: ...ir work Observe section 6 4 when putting the valve back into operation 8 0 Dismantling of the Valve In addition to the general installation guidelines and the operation safety order the following poin...

Страница 9: ...e all claims for damages against these companies will be voided 10 0 Explanations on Codes and Directives The Commission of the European Union has laid down common directives for the free trading of g...

Страница 10: ...13 Version 12 2015 TM 3926 11 0 Drawing 11 1 Fig 1 40 EVF NH DN15 DN25 55 EVF NH DN15 DN25 100 400 200 950 902 1 912 402 3 219 1 943 2 243 219 2 402 1 402 2 406 906 503 1 227 943 1 941 1 948 1 910 1 9...

Страница 11: ...er 110 1 Distanzst ck Spacer 120 1 Endschaltergeh use Limit switch housing 200 1 Ventilteller Valve disk 206 2 F hrungsring Guide ring 207 1 Magnetkern Solenoid core 210 5 Federbolzen Spring bolt 214...

Страница 12: ...906 1 Scheibe Washer 908 1 Sicherungsblech Safety plate 910 1 4 Zylinderschraube Cylinder screw 910 2 4 Zylinderschraube Cylinder screw 912 1 Splint Split pin 941 x 1 Gewindestift Setscrew 943 x 1 Sp...

Страница 13: ...ounting manual translation EVF _______________________________________________________________________________________________________ 220 100 112 07 Page 13 13 Version 12 2015 TM 3926 12 0 Declaratio...

Отзывы: