19-2021 Rev E, 06/05/07 

 
Never look at the lamps while illuminated.  Only view illumination by way of view port accessory.  
To prevent exposure to ultraviolet light, disconnect power to the V-Flex before servicing any part 
of the HVAC system. 
 

MOUNTING LOCATION 

 

CAUTION 

Equipment Damage Hazard 
Ultraviolet light can cause color shift or structural degradation of plastic 
HVAC materials.

 

 
Select mounting location that prevents exposure to plastic components with unknown resistance 
to ultraviolet light.  It is recommended that there be a minimum of three-feet between ultraviolet 
lamps and plastic-fabricated devices (such as non-fiberglass media filters). 
 

 

CAUTION 

Equipment Damage Hazard 
Ultraviolet light can cause color shift or surface degradation and 
sometimes structural degradation of non-metallic components.

   

 
Select a mounting location that prevents exposure to plastic flexible duct components, 
polyurethane foam insulation material, rubber hoses, wire insulation, etc.  If mounting options are 
limited, items above should be protected with ultraviolet resistant material such as aluminum foil, 
aluminum duct tape, or metallic shields or equivalent. 

 

 

1.  Inspect and determine an appropriate location inside the air handling system for the 

installation.  The location should allow for the mounting of a bracket on the floor and the 
ceiling of the air handler and should be readily accessible for the cleaning of lamps and 
the annual replacement of lamps (see Figure 2a).  

 
 

Record Dimensions: 

 

 

Figure 2a 

 

Dimension A Dimension B Dimension C

 

Содержание High Output UV Device V-Flex

Страница 1: ...05 07 1 V Flex High Output UV Device INSTALLER OWNER S GUIDE Specifications subject to change without notice Altru V and V Flex are brands owned by UVDI Copyright 2003 by UltraViolet Devices Inc All...

Страница 2: ...ING LOCATION 5 INSTALLATION OF THE LAMP MODULES 6 INSTALLATION OF THE POWER JUNCTION MODULE 8 INSTALLATION OF MAIN SUPPORT INTO AIR HANDLING DUCT 9 ELECTRICAL CONNECTION OF THE SYSTEM 10 LAMP INSTALLA...

Страница 3: ...to 135 F 4 C to 51 C Relative Humidity Up to 95 rh non condensing Power Consumption Model Input Current A Lamp Wattage W 120V 0 6 60 240V 0 3 60 Approvals Underwriters Laboratories File no E212213 Ca...

Страница 4: ...switches must be installed at any access panel or door within view of the UV fixtures 4 The installer must be a trained experienced service technician 5 After installation is complete check out produc...

Страница 5: ...pment Damage Hazard Ultraviolet light can cause color shift or surface degradation and sometimes structural degradation of non metallic components Select a mounting location that prevents exposure to...

Страница 6: ...ction of the Main Support using a tool appropriate for cutting aluminum Cut only from one end as it is important to retain a wiring feed through hole in the Main Support section to be installed Figure...

Страница 7: ...wires from the last Lamp Module installed to the Main Support through the strain relief and into the wiring compartment of the next Lamp Module 13 Route the external wires from the Lamp Module under...

Страница 8: ...ove Power Junction Module cover 22 Thread wires from last Lamp Module installed on each side through Power Junction Module strain relief See Figure 4a 23 Attach Power Junction Module to support with s...

Страница 9: ...ain Support for all gaps existing in the Main Support raceway INSTALLATION OF MAIN SUPPORT INTO AIR HANDLING DUCT 1 Carefully carry the partially assembled Main Support into the installation area 2 Pl...

Страница 10: ...skin and eyes Can cause temporary or permanent loss of vision Never look at the lamps while illuminated Only view illumination by way of view port accessory To prevent exposure to ultraviolet light d...

Страница 11: ...19 2021 Rev E 06 05 07 11...

Страница 12: ...module so that is holding the lamp in place and the clip is secured onto the metal module Make sure the clip is slid over the lamp module as shown below 3 Push the lamp in till it snaps into place Ver...

Страница 13: ...ook directly into the duct to see the illuminated ultraviolet lamp The installer should orient the owner to the unit by demonstrating use of the view port accessory and discussing how to determine whe...

Страница 14: ...ry If the air stream is filtered cleaning schedule may be reduced To clean the lamp 1 Disconnect power to HVAC system Never enter system with UV lamps illuminated 2 Open the system access panel or doo...

Страница 15: ...ert new lamp into the Lamp Module Depress lamp release button and insert lamp Let go of the lamp release button and verify that lamp is retained 6 Reconnect the power to the HVAC system 7 Clean the la...

Страница 16: ...NT EXCEED THE COST OF THE GOODS SOLD UNDER THIS CONTRACT OF SALE UVDI neither assumes nor authorizes any person to assume for it any obligation in connection with the goods This warranty shall not app...

Отзывы: