13
www.Ultra-Aire.com | 1-800-533-7533
Ultra-Aire 70H Installation Instructions
The Ultra-Aire 70H can be installed on multiple HVAC systems. Dehumidified air will be provided to both
HVAC systems for distribution throughout the structure.
• A backdraft damper is required in the supply ducts.
• DO NOT locate the return in a bathroom or kitchen.
• One control will service both HVAC zones. Control should be located remotely from the dehumidifiers and
placed in a central location.
• HVAC systems should be in close proximity for optimal air flow.
• For multiple systems, contact Technical Support at 1-800-533-7533.
DUCTING TO HVAC SYSTEMS
Recommended Multiple HVAC System Installation
HVAC
Supply
Ultra-Aire
Supply
Second Air Handler
Dedicated Ultra-Aire 90 Return to multi systems A/C Supply
HVAC Return
Backdraft
Damper
First Air Handler
HVAC Return
HVAC
Supply
Backdraft
Damper
Indoor
Air Return
Fresh Air Intake
(Optional)
Motorized
Damper
Dedicated Ultra-Aire Return to Multiple HVAC Systems
CAUTION!
DO NOT CONNECT WITH A STATIC PRESSURE GREATER THAN OR EQUAL TO +0.5 WG.
CONTACT TECHNICAL SUPPORT AT 1-800-533-7533 FOR ADDITIONAL DETAILS.