14
Ultra-Aire 70H Installation Instructions
www.Ultra-Aire.com | 1-800-533-7533
When installing the Ultra-Aire 70H in a structure that does not have a forced air HVAC system, a single
return for the Ultra-Aire 70H should be installed in a central location.
Install a 6" insulated duct from outside, teeing into the 8" return duct of the Ultra-Aire 70H to provide fresh
air ventilation (optional).
The supply of the Ultra-Aire 70H should be ducted to remote areas of the structure such as bedrooms, living
room, den, etc. Be sure to utilize multiple rooms to allow air inside the structure to properly circulate. Proper
air distribution is important to ensure even humidity control and heat distribution throughout the structure.
A 6" diameter duct is recommended for branches to bedrooms. An 8" diameter duct is recommended for
branches to larger areas.
• DO NOT locate the return in a bathroom or kitchen.
• DO NOT locate the supply in smaller rooms where doors may be closed.
• Control should be located remotely from the dehumidifier and placed in a central location.
Ultra-Aire
Air Supply
Indoor Air
Return
Optional Fresh
Air Intake
Motorized
Damper
DUCTING TO HVAC SYSTEMS
No Existing Ductwork Installation
No Existing Ductwork Installation