Ultra-Aire 70H Installation Instructions
www.Ultra-Aire.com | 1-800-533-7533
The Ultra-Aire 70H plugs into a common grounded 115VAC outlet. The device draws 5.1 Amps at 80°F and
60% RH. Locate the dehumidifier in an area where the cord’s length (9') easily reaches a 115 VAC electrical
outlet with a minimum of 15 Amp circuit capacity. If used in an area that may become wet, a GFCI protected
circuit is recommended. Consult local electrical codes for any further information.
Ultra-Aire offers a variety of control devices for use with the Ultra-Aire 70H. The controls are to be located
remotely from the dehumidifier and placed in the space to be conditioned. Low voltage (24 Volt) controls can be
used with the Ultra-Aire 70H and MUST be connected with low voltage (18-22 gauge) thermostat wire.
ELECTRICAL REQUIREMENTS
CAUTION!
DO NOT ALLOW THE YELLOW LEAD TO CONTACT THE RED LEAD ON THE ULTRA-AIRE 70H OR
DAMAGE TO THE TRANSFORMER WILL RESULT.
Electrical Precautions
• Do not install the control where it may not accurately sense the relative humidity such as near HVAC
supply registers, near exterior doors, on an outside wall, near a window, or near a water source.
• The control wires leaving the Ultra-Aire 70H and the control are numbered and color-coded to
prevent confusion.
• Be sure to consult the electrical schematic in the CONTROLS Section (page 21) of this manual or
inside the access panel of the Ultra-Aire 70H before making control connections.
WARNING!
THE REMOTE CONTROLS OF THE ULTRA-AIRE 70H ARE POWERED BY A LOW VOLTAGE CIRCUIT
(24VAC) AND MUST NEVER CONTACT OR BE CONNECTED TO A HIGH VOLTAGE CIRCUIT.
CAUTION!
SOME OF THE CONTROL WIRES LEAVING THE ULTRA-AIRE 70H MAY NOT BE USED WITH
CERTAIN CONTROLS AND SHOULD BE LEFT UNCONNECTED WITH WIRE NUTS TAPED ONTO
THE STRIPPED ENDS FOR SAFETY.
Wiring Schematic