- 3 -
Cisconnection detection
function
It is judged that it disconnects when becoming 「Input signal≦
-20%F.S.」 Rate mete and ratio“
- - - - -
blinking”
(A2,A3 type)
※ The disconnection detection can be output from OUT4(Option)
EXT. input
EXT input function
Hold/peak hold/bottom hold/width of input/0 adjustment
function.(
“mode №3” selectable)
The rear terminal board (6-7) is ON. 50mS or more is ON.
(HD turning on the lamp)
Input
NPN open collector pulse input or ground contact.
Preset
output
Output terminal
Output terminals no.1-2-3 (OUT1),14-15-16 (OUT2)
Comparative system
Upper limit, lower limit (immediately) and lower limit
(delay). (selectable)
Output mode
Comparison, maintenance,(selectable)
Output selection
Function stop, Rate mete, Raito,(selectable)
Preset value setting
The presetting program mode setting is also selectable.
Output judgment
Judgment output is compared with the indication value by
preset value.
Output circuit
Tow-row relay 1c output
[ Control capacity / Maximum permissible power ]
AC125V 0.6A (Resistance load)
AC250V 0.3A (Resistance load)
DC 30V 2A (Resistance load)/60W MAX
[ The maximum control current ]
2A MAX
※ Can be used within control current 2A and control capacity
/ permissible power.
Output indication
During presetting output, the OUT1 and OUT2 LED are activated
Output reset
The key to the pushed for 2 sec or more.
Hysteresis setting
0-3999 (4 digits to disregard decimal point)
Hysteresis operation
Invalid or selects it from effective.
※ When the output mode is only“Compareson”,it operates.
Preset output state
distinction time
It outputs it continuing set time (0.0-99.9 sec) after it
enters the output area at the output area.
Data backup
Each mode stting value is memorized by FRAM
(The memory number of times is within 100,000 times,
About 10 year safekeeping.)
Others
Mode protect function
Changes by mode protect function setting.
“L-oFF”is possible to change by setting.
“L-on”is not possible to change by setting.
Warm up time
After turning on the power, more than 30 minutes.
Power source
AC85-264V (50/60 Hz)
DC-type
DC12-24V (±10%)
Power consumption
Approx. 23VA
DC-type
Approx. 10W
Temperature/humidity
conditions
0-50 ℃, 30-80 %RH (Non-condensing)
Weight/dimensions
Approx. 370g, W96×H48×D130mm
Material of the case
ABS
Color
Gray
K-type
Black
Protection class
IP66
/75VA MAX
RST
Содержание LV1000 Series
Страница 16: ...12 The setting menu Each mode transition Preset value setting...
Страница 17: ...13 Mode setting Scaling setting...
Страница 18: ...14 Linearization setting 8 step preset value setting...
Страница 19: ...15 Test mode...
Страница 57: ...53 Analog adjustment mode flow chart...
Страница 64: ...60 Dimensions Fig 26...