UE 2W2D Скачать руководство пользователя страница 8

8

 

IM_ONE-01

 

www.ueonline.com

IMPORTANT NOTE: 

 

3-state switch (pulsed) modes must not be used when the switch output is connected directly to a load that could be damaged by being 

switched at the pulse frequency.  For these types of loads, use a 2-state mode.

SET POINT

:

The set point is the value at which the One Series changes the state of the output.  It is fully adjustable throughout the operating range of the unit (noted on the 
nameplate).  Model 8W2D has two independent set points, one for each switch output.

DEADBAND

:

Deadband is the amount above or below the set point at which the One Series changes the output state back to normal operation.  In rising modes of operation 
the deadband must be less than the set point. In falling modes of operation the deadband must be less than the operating range of the unit minus the set point.  
In the One Series menu, the deadband is represented as a value which is added or subtracted from set point, depending on control mode (e.g., if the Control Mode 
is “Open on Rise” and the set point is set at 100 psi with a deadband of 10, the output will open as the pressure rises through 100 psi and close as the pressure 
falls through 90 psi.  If the Control Mode is changed to “Open on Fall”, the output would open as the pressure falls through 100 psi and close as the pressure 
rises through 110 psi).  The deadband should be set wide enough so that frequent cycling or chatter does not occur, but narrow enough to satisfy conditions for 
normal process operation.  Model 8W2D has two independent deadband settings, one for each switch output.

Mode is changed to “Open on Fall”, the output would open as the pressure falls through 100 psi and close as the pressure rises through 110 psi).  The deadband 
should be set wide enough so that frequent cycling or chatter does not occur, but narrow enough to satisfy conditions for normal process operation.  Model 8W2D 
has two independent deadband settings, one for each switch output.

ADVANCED FEATURES

NOTE:

  No initial programming of these features is required.  The default for these advanced commands is zero or off.

MINIMUM & MAXIMUM READINGS:

The One Series continuously captures the readings from the sensor and stores the minimum and maximum values since the last time they were reset.  These can 
be viewed at any time by pushing the left        button.  The display will scroll the information and then return to the Process Display mode.  To reset these values, 
enter the Programming Mode (see page 6), use the left         button to get to the CLR MAX/MIN command and press the right        button two times.  After exiting 
the Programming Mode and saving the changes (see page 6), the values will be reset to the current reading and begin cumulative recording again.

OFFSET:

The One Series is factory calibrated to 0.5% of range at room temperature.  In some applications it may be necessary to re-calibrate the unit in the field.  Offset 
allows the user to enter a positive ("POS") or negative ("NEG") offset to the pressure readings.  An offset of up to +/- 10% of the range is allowed.

NOTE:

  Any numerical value entered other than 0.00 will cause the display to indicate “Offset” just above the process reading in the process display.

WARNING:  USE OF THIS OPTION MAY CREATE A CONDITION WHERE THE DISPLAY MAY INDICATE “0.00” WHEN SIGNIFICANT PRESSURE (10% OF RANGE) 
EXISTS  IN  THE  SYSTEM.    INDEPENDENT  VERIFICATION  OF  THE  SYSTEM  PRESSURE  SHOULD  BE  DONE  PRIOR  TO  MAINTENANCE  ON  THE  SYSTEM  IF 
“OFFSET” APPEARS ON THE PROCESS DISPLAY.

SPAN:

The SPAN adjustment allows the user to shift the slope of the calibration curve by +/- 10%.

To adjust Span a reference pressure near full scale should be applied to the unit.  The display value and the reference pressure should be noted. 

To calculate the number to enter for Span divide the reference pressure by the display reading, then multiply by the full scale pressure range of the One Series. 

Span value=(Reference Pressure / Display Reading) x Full Scale Pressure Range of the One Series.

Example:  One Series  

   

 

100 psi range

   

Reference Pressure    

=  

100 psi

   

Display Reading  

 

=  

 98 psi

   

100  x 100  =  102 (Enter this number for Span)

   

 98

NOTE:

 Span is limited to +/- 10% of the full scale range.  Entering a “0” will disable the feature.

WARNING:    USE  OF  THIS  OPTION  MAY  “DE-CALIBRATE”  THE  UNIT  TO  SUCH  A  CONDITION  THAT  THE  PROCESS  DISPLAY  MAY  INDICATE  “0.00”  WHEN 
SIGNIFICANT PRESSURE IS ACTUALLY PRESENT IN THE SYSTEM.  INDEPENDENT VERIFICATION OF THE SYSTEM PRESSURE SHOULD BE DONE PRIOR TO 
MAINTENANCE ON THE SYSTEM IF “OFFSET” APPEARS ON THE DISPLAY.

Содержание 2W2D

Страница 1: ...NS ONLY THIS EQUIPMENT IS ATEX CERTIFIED SUITABLE FOR APPROPRIATE USE IN GAS ZONE 2 DUST ZONE 22 APPLICATIONS OR GAS ZONE 0 DUST ZONE 20 APPLICATIONS WHEN INSTALLED PER DRAWING A 62174 20 EUROPE 0539 DEMKO 03 ATEX 0322281X 0539 DEMKO 03 ATEX 0322281X II 1 G EEx ia IIC T5 II 3 G EEx nL IIC T5 II 1 D T 90ºC II 3 D T 90ºC 40ºC TAMB 85ºC IP66 40ºC TAMB 85ºC IP66 2W3A MODELS THIS EQUIPMENT IS SUITABLE ...

Страница 2: ...lean and free of debris Use a wrench on the hex pressure connection to tighten Test for leaks On Differential Pressure models the Low L side pressure must NOT exceed the high H side pressure WARNING NEVER INSERT ANY OBJECT INTO THE PRESSURE SENSOR OPENING DAMAGE TO THE SENSOR WILL RESULT AFFECTING ACCURACY Local and Remote Temperature Models For Remote Sensing models C H R Route the extension wire...

Страница 3: ... PAGE 12 FOR ADDITIONAL INFORMATION ON SELECTING AN INTRINSIC SAFETY BARRIER SUBSTITUTION OF COMPONENTS MAY IMPAIR INTRINSIC SAFETY WARNING MODEL 4W3A ACCEPTS 90 130 VAC VDC AS ITS POWER SOURCE THE SWITCHED OUTPUT MAXIMUM LOAD RATING IS 10 A 24 280 VAC AT T amb 38 C 100 F DERATE 1 8 A 10 C 18 F OVERLOADING THE SWITCH MAY CAUSE FAILURE WARNING THE ONE SERIES 8W2D MODEL ACCEPTS 12 30 VDC AS ITS POWE...

Страница 4: ...L1 and L2 terminals Connect the potential free solid state relay at TB1 to an appropriate load Refer to the Switch Ratings Table for the switch ratings The 4W3A has one terminal block labeled TB1 TB1 has four positions marked with L1 L2 and a switch symbol covering the remaining two positions TB1 terminal block accepts 14 22 AWG wiring and the recommended torque is 3 5 in lbs The 8W2D has three te...

Страница 5: ...switch is fully programmable over the entire range of the sensor Reaction time for the One Series to a process change is typically 50 mS or less 2 WIRE SIMPLICITY 2W Models only The One Series 2 Wire electronic pressure switch patented is designed to operate on discrete input leakage current models 2W2D and 2W3A or analog input 4 20 mA loop power models 2WLP41 and 2WLP43 The microprocessor based O...

Страница 6: ...ription of Offset and Span In addition the user can easily access information such as the set point dead band and minimum maximum process readings By pushing the right button once the display will scroll as follows SP1 XX XX DB1 XX XX SP2 XX XX DB2 X XX 8W2D model only By pushing the left button once the display will scroll the min max process values seen MAX XX XX MIN XX XX The display will rever...

Страница 7: ... confirm save the changes and return to the Process Display mode to Discard changes press the right button NO will be displayed Press both buttons to confirm discard the changes and return to the Process Display mode KEY PROGRAMMING FEATURES SWITCH MODE The One Series allows the switch output to be set up for either 3 state I Am Working or 2 state operation For an overview of the I Am Working IAW ...

Страница 8: ...usly captures the readings from the sensor and stores the minimum and maximum values since the last time they were reset These can be viewed at any time by pushing the left button The display will scroll the information and then return to the Process Display mode To reset these values enter the Programming Mode see page 6 use the left button to get to the CLR MAX MIN command and press the right bu...

Страница 9: ...resents the expected variation in the process variable The number is limited to 10 of the full scale range of the sensor The diagram below illustrates the feature s operation T0 Process variable ramp up T1 Process variable stabilizes new thresholds calculated T2 Threshold exceeded new thresholds calculated timer reset T3 Low threshold exceeded new thresholds calculated timer reset T4 Plugged Port ...

Страница 10: ... diagnostics are capable of detecting many possible fault conditions Some fault conditions will clear automatically when the parameter returns to normal others require the unit to be powered down and restarted and some are catastrophic and require repair or replacement A list of fault conditions is shown below DISPLAY WILL SCROLL FAULT RESULT SWITCH OUTPUT 4 20 mA OUTPUT PLUG Plugged Port Detected...

Страница 11: ...an help Please have the manufacturer s model number ready when you call us In rare cases when the series resistor value is too large and falls out of the Acceptable Range placing another resistor across the input will allow it to work Please call 617 926 1000 Technical Sales for assistance Please note that a maximum of 30 VDC supply voltage and a load of 40 mA must not be exceeded or permanent dam...

Страница 12: ...ty barriers must be installed with a suitable 1Ω earth ground Isolated barriers offer simplified installation since there is no requirement for the ground but are generally more expensive than the diode safety barriers Shunt Diode Safety Barriers The entity parameters of diode safety barriers suitable for use with the 2W2D models are V max 28 Volts I max 93 mA Because the 2W2D model derives its op...

Страница 13: ...IM_ONE 01 13 www ueonline com PROCESS DISPLAY ...

Страница 14: ...14 IM_ONE 01 www ueonline com Models 8W2D and 2WLP Dual Conduit shown with Temperature Sensor Models 4W3A 2W2D and 2W3A Single Conduit shown with Gauge Pressure Sensor DIMENSIONAL DRAWINGS ...

Страница 15: ...IM_ONE 01 15 www ueonline com Temperature Model L Temperature Model R SENSOR OPTIONS Gauge Pressure 1 2 NPT female Temperature Models H C Differential Pressure ...

Страница 16: ...ca tions where damage could endanger property or personnel Electrical ratings stated in literature and on nameplate must not be exceeded Overload on a switch can cause damage even on the first cycle Wire unit according to local and national electrical codes using wire size recommended in installation sheet Do not mount unit in ambient temp exceeding published limits LIMITED WARRANTY Seller warrant...

Отзывы: