4
IM_ONE-01
www.ueonline.com
Model 2W2D
is intended for direct connection to a 24 VDC PLC or DCS discrete input, or other
suitable load (see page 11). Power is obtained and the switch is provided by the same two-wire
connection. Polarity must be observed. Refer to the Switch Ratings Table for the switch ratings.
Do not connect this model directly to a power supply.
Model 2W3A
is intended for direct connection to a 115 VAC or VDC PLC or DCS discrete input,
or other suitable load (see page 11). Power is obtained and the switch is provided by the same
two-wire connection. Refer to the Switch Ratings Table for the switch ratings.
Do not connect
this model directly to a power supply.
Model 2WLP
is loop-powered and is connected directly to an analog input of a PLC or DCS via
TB2 providing a 4-20 mA analog signal (see page 11). Polarity must be observed. The auxiliary
solid-state relay is connected via TB1. Refer to the Switch Ratings Table for the switch ratings.
Model 4W3A
requires a 90-130 VAC @ 15 mA external power supply. Connect the leads from
the power supply to TB1 L1 and L2 terminals. Connect the potential-free solid-state relay at TB1
to an appropriate load. Refer to the Switch Ratings Table for the switch ratings.
The 4W3A has one terminal block labeled TB1. TB1 has four positions, marked with “L1”, “L2” and a switch symbol covering the remaining two positions. TB1
terminal block accepts 14-22 AWG wiring and the recommended torque is 3.5 in-lbs.
The 8W2D has three terminal blocks, one located on the back of the display module and two, labeled TB1 and TB2, located on circuit board permanently mounted
inside the enclosure. The display module terminal block accepts 14-22 AWG wiring and the recommended torque is 7 in-lbs. TB1 has two positions marked “4-
20+” and 4-20-”. These markings indicate the polarity of the 4-20 mA analog signal. Polarity must be observed. TB1 terminal block accepts 14-26 AWG wiring
and the recommended torque is 4.38 in-lbs. TB2 has five positions, four marked with a switch symbol and one marked with a chassis ground symbol. TB2 terminal
block accepts 14-22 AWG wiring and the recommended torque is 3.48 in-lbs.
NOTE:
The sensor wiring harness must be connected to the module with the red wire oriented to the arrow on the label. Reversing this connector will result in
measurement errors or failure.
WIRING DIAGRAMS