IM_ONE-01
www.ueonline.com
LADDER LOGIC EXAMPLE
(used for detecting the pulsed output)
Ladder logic for One Series 2-wire model 2W2D
Pulse-on-rise output (25 mSec)
SELECTING AN INTRINSIC SAFETY BARRIER
(Model 2W2D only)
WARNING: INSTALLATION OF INTRINSICALLY SAFE CIRCUITS MUST BE PERFORMED IN ACCORDANCE WITH THE REQUIREMENTS OF THE GOVERNMENT
AND/OR OTHER LOCAL AUTHORITY HAVING JURISDICTION. SYSTEM COMPONENTS AND INSTALLATION METHODS MUST BE APPROVED BY THE APPROPRI-
ATE RECOGNIZED APPROVAL AUTHORITY.
The information provided below is for reference only and is intended to act as a guide in the selection of a suitable I.S. Barrier. Please reference one of the
following I.S. control drawings for installation details and device entity parameters:
A-62174-19
(North American, Class, Division & Zone based installations)
A-62174-20
(European, Class, Zone based installations)
There are two general types of Intrinsic Safety Barriers, shunt diode (passive) safety barriers and transformer isolated barriers. Shunt diode safety barriers are
the simplest and least expensive type of I.S. interface for protecting circuits in hazardous areas. Diode safety barriers must be installed with a suitable (<1Ω)
earth ground. Isolated barriers offer simplified installation, since there is no requirement for the ground, but are generally more expensive than the diode safety
barriers.
Shunt Diode Safety Barriers:
The entity parameters of diode safety barriers suitable for use with the 2W2D models are:
V max = 28 Volts
I max = 93 mA
Because the 2W2D model derives its operating power from the input of the host device to which it is connected it is also important to select a barrier with a low
leakage current. This is typically specified as V
wkg
, the working voltage , at which 10 uA of leakage current will occur.
V
wkg
> 25 Volts; at 10 uA of leakage current is ideal
Suggested Sources:
P Fuchs
®
Model No. Z787
MTL
®
Model No. 7087+
Transformer Isolated Barriers:
Due to the unique method by which the model 2W2D operates, a specifically designed isolated barrier must be used:
(Contact United Electric Controls for pricing and availability: (617)926-1000 Tech. Sales)
The isolated barrier is available from UE, your distributor, or MTL:
(Choose One)
• Order UE Part Number 62169-29 for the Barrier packaged separately from UE or your distributor, or
• Order Option Code M036 for the Barrier packed with the 2W2D model from UE or your distributor, or
• Order Part Number MTL 5012S directly from MTL or any of its distributors.