IM_ONE-01
3
www.ueonline.com
WIRING
Tools Required
Phillips-head screwdriver
Small slotted screwdriver
Wire strippers
WARNING: EXPLOSION HAZARD - DO NOT REPLACE COMPONENTS UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NON-
HAZARDOUS.
WARNING: EXPLOSION HAZARD - DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NON-
HAZARDOUS
WARNING: TO MAINTAIN ENCLOSURE INTEGRITY FRONT DISPLAY SCREWS ARE TO BE TORQUED AT 4 IN-LBS (0.45 N-m) IN END USE APPLICATION.
WARNING: THE DEVICES SHALL BE PROPERLY GROUNDED IN THE END USE APPLICATION.
WARNING: LEADWIRES MUST BE RATED 75°C MINIMUM COPPER CONDUCTOR ONLY.
WARNING: MODEL 2W2D ACCEPTS 12-30 VDC AS ITS POWER SOURCE, DIRECTLY FROM DIGITAL INPUTS TO PLCS, DCSS AND OTHER LOW-POWER DC LOADS.
THE SWITCHED OUTPUT MAXIMUM LOAD RATING IS 40 mA. (THE UNIT MUST NOT BE CONNECTED DIRECTLY TO A POWER SUPPLY WITHOUT AN APPROPRI-
ATE CURRENT LIMITING LOAD SUCH AS THAT PROVIDED BY A PLC/DCS DISCRETE INPUT.
OVERLOADING THE SWITCH MAY CAUSE FAILURE.
WARNING: MODEL 2W3A ACCEPTS 90-130 VAC/VDC AS ITS POWER SOURCE, DIRECTLY FROM DISCRETE INPUTS TO PLCS, DCSS AND OTHER LOW-POWER
LOADS. THE SWITCHED OUTPUT MAXIMUM LOAD RATING IS 100 mA. THE UNIT MUST NOT BE CONNECTED DIRECTLY TO A POWER SUPPLY WITHOUT
AN APPROPRIATE CURRENT LIMITING LOAD SUCH AS THAT PROVIDED BY A PLC/DCS DISCRETE INPUT.
OVERLOADING THE SWITCH MAY CAUSE
FAILURE.
WARNING:
MODEL 2WLP IS LOOP-POWERED AND OBTAINS POWER FROM THE 4-20 mA LOOP. THE 2WLP41 SWITCHED OUTPUT MAXIMUM LOAD RATING
IS 0.6 A @ 140 VDC OR VAC AND 0.3 A @ 280 VDC OR VAC FOR MODEL 2WLP43. OVERLOADING THE SWITCH MAY CAUSE FAILURE.
THE SWITCH MUST
NOT BE CONNECTED DIRECTLY TO A POWER SUPPLY.
WARNING: FOR INTRINSICALLY-SAFE INSTALLATIONS, PLEASE REFERENCE THE CONTROL DRAWINGS (UE 62174-19 NORTH AMERICA OR 62174-20
EUROPE) FOR INTRINSIC SAFETY ENTITY PARAMETERS AND OTHER NECESSARY INFORMATION. UNIT MUST BE WIRED TO AN APPROVED I.S. BARRIER.
REFER TO PAGE 12 FOR ADDITIONAL INFORMATION ON SELECTING AN INTRINSIC SAFETY BARRIER. SUBSTITUTION OF COMPONENTS MAY IMPAIR
INTRINSIC SAFETY.
WARNING: MODEL 4W3A ACCEPTS 90-130 VAC/VDC AS ITS POWER SOURCE. THE SWITCHED OUTPUT MAXIMUM LOAD RATING IS 10 A, 24-280 VAC AT
T(amb) 38°C (100°F). DERATE 1.8 A/10°C (18°F).
OVERLOADING THE SWITCH MAY CAUSE FAILURE.
WARNING:
THE ONE SERIES 8W2D MODEL ACCEPTS 12-30 VDC AS ITS POWER SOURCE. THE MAXIMUM LOAD RATING FOR EACH SWITCH IS SHOWN IN
THE TABLE ON PAGE 5.
OVERLOADING THE SWITCH MAY CAUSE FAILURE.
Remove the four (4) Phillips-head screws holding the faceplate to the enclosure. Gently remove the faceplate module. Exercise caution so that the wires going
between the sensor and the faceplate module are not damaged or removed. Locate field wires and strip carefully. Insert field wiring per the diagrams on page 4.
Carefully place the faceplate back on the enclosure and re-attach using the (4) Phillips screws (4 in-lbs or 0.45 N-m). DO NOT OVERTIGHTEN.
Terminal Block and Torque Details
The 2W2D terminal block is marked “+” and “-”, and includes a chassis ground symbol. These markings indicate the polarity of this polarized switch. Polarity
must be observed or the 2W2D will not work, making it necessary to reverse the wiring connections. The 2W2D is reverse polarity protected, so no damage
results from miswiring. The 2W2D terminal block accepts 14-22 AWG wiring and the recommended torque is 7 in-lbs.
The 2W3A terminal block is market “~” and “~”, and includes a chassis ground symbol. The 2W3A is a non-polarized switch, so connections can be made to
either terminal without observing polarity. The 2W3A terminal block accepts 14-22 AWG wiring and the recommended torque is 7 in-lbs.
The 2WLP has two terminal blocks, TB1 and TB2. TB1 has three positions, two marked with a switch symbol and one marked with a chassis ground symbol. TB1
terminal block accepts 14-22 AWG wiring and the recommended torque is 3.48 in-lbs. TB2 has two positions marked “4-20+” and
4-20-”. These markings indicate the polarity of the 4-20 mA analog signal. Polarity must be observed. TB2 terminal block accepts 14-26 AWG wiring and the
recommended torque is 4.38 in-lbs.