Model 8W2D

 requires a 12-30 VDC @ 30 mA external power supply. Connect the leads from the 

power supply to the + and - terminals on the back of the 8W display module, observing polarity. 
Connect the 4-20 mA output available at TB1 to an appropriate analog input, observing polarity. 
Connect the two potential-free solid-state relays at TB2 to appropriate loads. Refer to the Switch 
Ratings Table for SW1 & SW2 ratings. 

Switch Ratings Table

Model Number

SW1

SW2

2W2D00

12-30 VDC @ 40 mA

N/A

2W3A00

90-130 VAC/VDC @ 100 mA

N/A

2WLP41

0-140 VAC/VDC @ 0.6 A 

1

N/A

2WLP43

0-280 VAC/VDC @ 0.3 A 

1

N/A

4W3A01

24-280 VAC @ 10 A 

2

N/A

8W2D42

75-250 VAC @ 1.5 A 

3

75-250 VAC @ 1.5 A 

3

8W2D44

75-250 VAC @ 1.5 A 

3

0-140 VAC/VDC @ 0.6 A 

1

8W2D45

0-140 VAC/VDC @ 0.6 A 

1

0-140 VAC/VDC @ 0.6 A 

1

Warning:

 

Exceeding the current or voltage ratings could damage the One Series

 

 

Derate at 8% per 10°C (18°F)

2

 Derate at 1.8 A per 10°C (18°F) for temperature above 100°F (38°C)

3  

Derate at 10% per 10°C (18°F) (Subject to change)

THEORY OF OPERATION

The One Series electronic switch product line is based on an all-solid-state electronic module that incorporates a microprocessor.  The combination of features 
such as no moving parts and IAW

®

 self-diagnostics provide a highly reliable, accurate and repeatable monitor for detecting pressure and temperature thresholds 

and, once reached, can make intelligent switch decisions based on retained settings and current conditions.  Where a mechanical device has no way of determin-
ing its “readiness”, the One Series monitors its own health and reports it locally.  This IAW

®

 (I Am Working) feature provides a solution to the “blind device” issue 

common with mechanical apparatus.  You will always know the health status of the One Series.

The One Series is also very rugged, featuring a Enclosure Type 4X, weather-tight enclosure suitable for harsh environments and hazardous (Class I, Division 2) 
locations.  The 0.5% accuracy rating is maintained over a very wide -40°C - (+70°C) operating range using active temperature compensation.  Repeatability 
rivals that of a process transmitter, with a 0.1% of full range rating.  The set point and deadband (hysteresis) of the switch is fully programmable over the entire 
range of the sensor.  Reaction time for the One Series to a process change is typically 50 mS or less.

2-WIRE SIMPLICITY

 (2W Models only)

The One Series 2-Wire electronic pressure switch (patented) is designed to operate on discrete input leakage current (models 2W2D and 2W3A) or analog input 
4-20 mA loop power (models 2WLP41 and 2WLP43).  The microprocessor-based One Series 2-Wire is the only electronic switch to operate and switch over a 
single pair of wires, similar to a traditional mechanical switch or 4-20 mA process transmitter.  It combines the simplicity and low cost features of a switch and 
the reliability features of a transmitter, at less than half the price of the transmitter, and without the need to pull additional wiring.

•  Model 2W2D00 is designed to work with most 24 VDC discrete Programmable Logic Controller (PLC) or Distributed Control System (DCS) inputs and some  
  relays.  When open, the switch draws 350 µA; when closed the switch sinks or sources 40 mA maximum @ 12-30 VDC.
•  Model 2W3A00 is designed to work with most 115 VAC discrete PLC or DCS inputs and some relays.  When open, the switch draws 1 mA; when closed, the  
  switch sinks or sources 100 mA maximum @ 90-130 VAC or VDC.
•  Model 2WLP4x is loop-powered and operates in a transmitter loop attached to an analog PLC or DCS input and provides a field-scalable 4-20 mA signal over  
  a 2-wire connection.  Model 2WLP41 contains an auxiliary solid-state relay switch rated for 0.6 A @ 140 VAC or VDC maximum and requires 2 additional  
  wires, if used.  Model 2WLP43 is rated for 0.3 A @ 280 VAC or VDC.  

DISPLAY

The One Series features a large, easy-to-read display, showing the process condition and the status of the instrument. (See Display Features for a complete 
description.)  Set point, deadband and minimum/maximum process values can be easily accessed from the front of the unit while in operation.  Programming and 
interrogating the One Series is done through two buttons on the faceplate.

HIGH-POWER AND DUAL SWITCHING

One Series model 4W3A incorporates a relay to provide a high-capacity switch rating of 280 VAC at up to 10 A.  One Series model 8W2D provides 2 independent 
relays (see table on page 5 for details) and includes a field-scalable 4-20 mA analog output that is proportional to the process variable.  These One Series 
Models require a separate power supply.

Содержание 2W2D

Страница 1: ...NS ONLY THIS EQUIPMENT IS ATEX CERTIFIED SUITABLE FOR APPROPRIATE USE IN GAS ZONE 2 DUST ZONE 22 APPLICATIONS OR GAS ZONE 0 DUST ZONE 20 APPLICATIONS WHEN INSTALLED PER DRAWING A 62174 20 EUROPE 0539 DEMKO 03 ATEX 0322281X 0539 DEMKO 03 ATEX 0322281X II 1 G EEx ia IIC T5 II 3 G EEx nL IIC T5 II 1 D T 90ºC II 3 D T 90ºC 40ºC TAMB 85ºC IP66 40ºC TAMB 85ºC IP66 2W3A MODELS THIS EQUIPMENT IS SUITABLE ...

Страница 2: ...lean and free of debris Use a wrench on the hex pressure connection to tighten Test for leaks On Differential Pressure models the Low L side pressure must NOT exceed the high H side pressure WARNING NEVER INSERT ANY OBJECT INTO THE PRESSURE SENSOR OPENING DAMAGE TO THE SENSOR WILL RESULT AFFECTING ACCURACY Local and Remote Temperature Models For Remote Sensing models C H R Route the extension wire...

Страница 3: ... PAGE 12 FOR ADDITIONAL INFORMATION ON SELECTING AN INTRINSIC SAFETY BARRIER SUBSTITUTION OF COMPONENTS MAY IMPAIR INTRINSIC SAFETY WARNING MODEL 4W3A ACCEPTS 90 130 VAC VDC AS ITS POWER SOURCE THE SWITCHED OUTPUT MAXIMUM LOAD RATING IS 10 A 24 280 VAC AT T amb 38 C 100 F DERATE 1 8 A 10 C 18 F OVERLOADING THE SWITCH MAY CAUSE FAILURE WARNING THE ONE SERIES 8W2D MODEL ACCEPTS 12 30 VDC AS ITS POWE...

Страница 4: ...L1 and L2 terminals Connect the potential free solid state relay at TB1 to an appropriate load Refer to the Switch Ratings Table for the switch ratings The 4W3A has one terminal block labeled TB1 TB1 has four positions marked with L1 L2 and a switch symbol covering the remaining two positions TB1 terminal block accepts 14 22 AWG wiring and the recommended torque is 3 5 in lbs The 8W2D has three te...

Страница 5: ...switch is fully programmable over the entire range of the sensor Reaction time for the One Series to a process change is typically 50 mS or less 2 WIRE SIMPLICITY 2W Models only The One Series 2 Wire electronic pressure switch patented is designed to operate on discrete input leakage current models 2W2D and 2W3A or analog input 4 20 mA loop power models 2WLP41 and 2WLP43 The microprocessor based O...

Страница 6: ...ription of Offset and Span In addition the user can easily access information such as the set point dead band and minimum maximum process readings By pushing the right button once the display will scroll as follows SP1 XX XX DB1 XX XX SP2 XX XX DB2 X XX 8W2D model only By pushing the left button once the display will scroll the min max process values seen MAX XX XX MIN XX XX The display will rever...

Страница 7: ... confirm save the changes and return to the Process Display mode to Discard changes press the right button NO will be displayed Press both buttons to confirm discard the changes and return to the Process Display mode KEY PROGRAMMING FEATURES SWITCH MODE The One Series allows the switch output to be set up for either 3 state I Am Working or 2 state operation For an overview of the I Am Working IAW ...

Страница 8: ...usly captures the readings from the sensor and stores the minimum and maximum values since the last time they were reset These can be viewed at any time by pushing the left button The display will scroll the information and then return to the Process Display mode To reset these values enter the Programming Mode see page 6 use the left button to get to the CLR MAX MIN command and press the right bu...

Страница 9: ...resents the expected variation in the process variable The number is limited to 10 of the full scale range of the sensor The diagram below illustrates the feature s operation T0 Process variable ramp up T1 Process variable stabilizes new thresholds calculated T2 Threshold exceeded new thresholds calculated timer reset T3 Low threshold exceeded new thresholds calculated timer reset T4 Plugged Port ...

Страница 10: ... diagnostics are capable of detecting many possible fault conditions Some fault conditions will clear automatically when the parameter returns to normal others require the unit to be powered down and restarted and some are catastrophic and require repair or replacement A list of fault conditions is shown below DISPLAY WILL SCROLL FAULT RESULT SWITCH OUTPUT 4 20 mA OUTPUT PLUG Plugged Port Detected...

Страница 11: ...an help Please have the manufacturer s model number ready when you call us In rare cases when the series resistor value is too large and falls out of the Acceptable Range placing another resistor across the input will allow it to work Please call 617 926 1000 Technical Sales for assistance Please note that a maximum of 30 VDC supply voltage and a load of 40 mA must not be exceeded or permanent dam...

Страница 12: ...ty barriers must be installed with a suitable 1Ω earth ground Isolated barriers offer simplified installation since there is no requirement for the ground but are generally more expensive than the diode safety barriers Shunt Diode Safety Barriers The entity parameters of diode safety barriers suitable for use with the 2W2D models are V max 28 Volts I max 93 mA Because the 2W2D model derives its op...

Страница 13: ...IM_ONE 01 13 www ueonline com PROCESS DISPLAY ...

Страница 14: ...14 IM_ONE 01 www ueonline com Models 8W2D and 2WLP Dual Conduit shown with Temperature Sensor Models 4W3A 2W2D and 2W3A Single Conduit shown with Gauge Pressure Sensor DIMENSIONAL DRAWINGS ...

Страница 15: ...IM_ONE 01 15 www ueonline com Temperature Model L Temperature Model R SENSOR OPTIONS Gauge Pressure 1 2 NPT female Temperature Models H C Differential Pressure ...

Страница 16: ...ca tions where damage could endanger property or personnel Electrical ratings stated in literature and on nameplate must not be exceeded Overload on a switch can cause damage even on the first cycle Wire unit according to local and national electrical codes using wire size recommended in installation sheet Do not mount unit in ambient temp exceeding published limits LIMITED WARRANTY Seller warrant...

Отзывы: