Doc. 83779T – Rev. 03/10/18           

           3 - 8 

 

                  Dis. 24978/b 

 
 
 
 
 
The control unit manages 2 actuators so that, if one 
of the 2 breaks and causes a stopping in power 
absorption, also the one still running is stopped. 
The blocking time of the working actuator can be 
selected throught the“Dip Switch” SW1 for the 
opening and SW2 for the closing within 4 time 
modes from about a minimum of 0.5 seconds to 4 
seconds. The blocking function is disabled by 
switching OFF all the dip switches. 

 

POWER SUPPLY (CN1)

 

The CN1 power supply terminal must be plugged 
into the mains at 230 VAC 50/60 Hz. 

 

CAUTION:  
1) before opening the lid disconnect the 
unit from the power supply using an 
omnipolar system (electrically-powered 
parts inside). 
2) first connect all the earth conductors 
using the supplied terminal.
 

 

CONTROL (CN2)

 

For opening or closing controls use “free” contacts in 
CN2 terminal “OP COM CH”. 

 

Opening control (OP): 
Connect a button or a switch between COM pin and 
OP pin. 

 

Closing control (CL): 
Connect a button or a switch between COM pin and 
CH pin. 

 

When more control units are connected in 
parallel contact our technical office.

 

 
 

ACTUATOR OUTPUTS (MOT1-MOT2)

 

The control unit is fitted with two outputs MOT1 and 
MOT2. 
Each output is connected to an actuator at 230 VAC 
with three-wire control (common contact, Opening, 
and Closing). 
The two outputs are suitable for 230 VAC actuators 
with asynchronous motors of rated power 
consumption between 0.5 A – 1 Ampere.

 

 

CAUTION:  
Connect first all the earth conductors using the 
supplied terminal. 

 
 

“PARALLEL” OUTPUT (CN5)

 

The output connected pin-to-pin to another control 
unit uses multiple actuators in pair (also for the same 
window) and in case of sudden failure of any of the 
actuators it will block the others. 

 

CAUTION: 
FOR CONNECTION IN PARALLEL 
OBSERVE THE POWER SUPPLY 
CONNECTIONS “N” AND “L”, “PARALLEL” 
AND “CN2” TERMINALS.

 

 
 

 

 

IN THE EVENT OF ANY REVERSE 
CONNECTIONS THE CONTROL UNIT MAY 
NOT WORK OR WILL CAUSE A SHORT 
CIRCUIT.

 

 

A 5-pole cable for the AP-COM-CH control 
and the PARALLEL connection is 
recommended using the “Parallel” function. 
 
When more control units are connected in 
parallel contact our technical office. 

 

ACTUATOR STOP DELAY SETTING 

(SW1-SW2) 

SW1 selects the stop delay time of the actuator in 
case the other actuator connected with the control 
unit unexpectedly stops during the Opening control 
phase. 

 

SW2 selects the stop delay time of the actuator in 
case the other actuator connected with the control 
unit unexpectedly stops during the Closing control 
phase. 

 

The stop delay time through micro-switches has 5 
steps as reported below:

 

 

SW1/SW2 

Disab. 

0,5s 

1,5s 

3s 

4s 

Off 

Off 

Off 

Off 

On 

Off 

Off 

Off 

On 

Off 

Off 

Off 

On 

Off 

Off 

Off 

On 

Off 

Off 

Off 

 

The control unit has SW1/SW2 dip4 ON factory 
default setting.

 

 

GUARANTEE

 

Ultraflex Control Systems S.r.l. products are 
guaranteed, for a period of two years from the 
manufacture date, against defects in material and 
workmanship. 
Alleged defective products returned, freight prepaid, 
within the above said term, will be repaired or 
replaced free of charge, at our option, if found 
effectively below our quality standards. 
This guarantee does not cover other claims for direct 
or indirect damages. 
In particular, we decline liability and exclude 
guarantee (except for what stated above) if improper 
installation or misuse should result in a failure of our 
products.

 

 

CORRECT DISPOSAL OF THIS 

PRODUCT

 

The correct disposal of your old appliance will help 
prevent potential negative consequences for the 
environment. 

 
 
 
 
 
 
 
 
 

English

 

Содержание CP230

Страница 1: ...OPPIA DI ATTUATORI UCS A 230 Vca CONTROL PANEL FOR A COUPLE OF UCS 230 Vac ACTUATORS BO TIER DE COMMANDE POUR COUPLE D ACTIONNEURS UCS 230 Vca TANDEMABSCHALTUNG ZENTRALE F R ZWEI 230 Vac ANTRIEBE CENT...

Страница 2: ...ENTAZIONE N E L QUELLI DI PARALLEL E DEI MORSETTI CN2 SE I COLLEGAMENTI VENGONO IN QUALCHE MODO INVERTITI LA CENTRALE PUO NON FUNZIONARE OPPURE CAUSARE CORTO CIRCUITO Nel caso di utilizzo della funzio...

Страница 3: ...ase of sudden failure of any of the actuators it will block the others CAUTION FOR CONNECTION IN PARALLEL OBSERVE THE POWER SUPPLY CONNECTIONS N AND L PARALLEL AND CN2 TERMINALS IN THE EVENT OF ANY RE...

Страница 4: ...D ALIMENTATION N ET L LA CONNEXION PARALLEL ET CELLE DES BORNES CN2 I LES CONNEXIONS SONT INCORRECTES LE BO TIER PEUT NE PAS FONCTIONNER OU PROVOQUER UN COURT CIRCUIT En cas d utilisation de la foncti...

Страница 5: ...CKSICHTIGT WERDEN WENN DIE ANSCHL SSE AUF IRGEND EINE WEISE UMGEKEHRT WERDEN KANN ES SEIN DASS DIE ZENTRALE NICHT FUNKTIONIERT ODER EIN KURZSCHLUSS VERURSACHT WIRD Bei Einsatz der Funktion Parallel w...

Страница 6: ...LOS BORNES CN2 SI LAS CONEXIONES SON INVERTIDAS DE ALG N MODO LA CENTRALITA PUEDE CAUSAR CORTOCIRCUITO O NO FUNCIONAR En caso de utilizar la funci n Parallel se aconseja utilizar un cable de 5 polos p...

Страница 7: ...Doc 83779T Rev 03 10 18 7 8 Dis 24978 b SINTESI 2000 MAX SUPERMASTER 230 Vac...

Страница 8: ...contact our technical office S il est n cessaire de brancher plusieurs bo tiers en parall le contacter notre bureau technique Sofern mehrere Zentrale parallel geschaltet werden sollen wenden Sie sich...

Отзывы: