UC Living Rosmore SLIDE CONTROL Maintenance Instructions  

 

SECTION TEN Maintenance Instructions

 

 

GENERAL 

Servicing should be carried out annually by a competent person such as a Gas Safe -registered 
person in  accordance with the current  Gas Safety (Installation and Use) Regulations 1998 (as 
amended), this should ensure the safe and correct operation of the appliance. 
Before  commencing  any  service  or  replacement  of  parts,  turn  off  the  gas  supply  to  the  fire.  
After servicing check for gas soundness. 
When  ordering  spare  parts  please  quote  appliance  name  and  serial  number,  these  can  be 
found on the data badge, which is located by removing the decorative fire trim.  
At least once a year, check for debris in the catchment area behind the fire and in the flue way. 
If  soot  has  accumulated  check,  to  establish  cause,  rectify  and  clean  flue  or  chimney 
accordingly. 
 

FUEL BED CLEANING 
Important:  - 

Refer  to  the  ‘Health  &  Safety  Notice  located  on  page  3  of  this 

booklet

 

before cleaning or replacing any refractory material. 

 
The fuel bed components are delicate and they should be handled with great care. 
The loose parts and moulded shapes may be removed for cleaning. They can be brushed very 
gently  with  a  soft brush  to  remove  dust  or  any  deposits.  A  vacuum  cleaner  may  only  be  used 
after the loose components have been removed. 
Examine  the  fuel  bed  components  for  signs  of  cracking  and  replace  if  necessary. 
(IMPORTANT)  see  fuel  bed  layout  procedure  before  attempting  to  replace  loose  fuel  bed 
components, which should only be replaced as a complete set with no extra components. 

PILOT LINTING 

Check pilot aeration holes for linting,  use a  vacuum cleaner nozzle taking care not to damage 
the pilot head. (This should be done every time the fire is serviced) 
 

REPLACEMENT OF GAS CONTROL 

 
1. 

Turn off the gas supply by isolating cock. 

2. 

Lift away carefully fire fret. 

3. 

Lift away carefully all loose fuel bed components. 

Lift away carefully base boards. 

Disconnect gas supply from inlet elbow of appliance (right of gas control) 

Undo and remove two lower screws from fixing plate at front of appliance. 

Undo and remove two screws securing the tray to the back support. 

Undo the nut at the lower end of the slide control lever and separate it from the link 

Lift away the appliance burner tray from the main casing.  

10 

Disconnect the three compression gas connections from the gas control. 

11 

Undo the thermocouple connection from the rear of the gas control tap. 

12 

Undo the screw in the centre of the gas control spindle and remove from linkage. 

13 

Undo and remove the two screws securing the gas control valve to assembly. 

14 

Service or replace gas control tap as necessary. 

15 

Re-assemble the in reverse order. 

16 

Turn on the gas supply, check for soundness and re commission appliance. 

 

 

 

Содержание Rosmore Slide Control

Страница 1: ...ES USER INSTALLATION MAINTENANCE INSTRUCTIONS Please read these instructions carefully before you start using the appliance Keep this booklet handy for future reference This appliance is for use in GR...

Страница 2: ...ments 13 Clearance to Shelf 13 Clearance to Side of Fire 14 Ventilation 14 SECTION NINE To Install the Appliance 14 Examine Flue Chimney 14 Connecting to the Gas Supply 14 Preparing the Appliance for...

Страница 3: ...andling wash hands and other exposed parts If a vacuum is used for cleaning the fuel bed or cleaning after servicing installation it is recommended that it be of the type fitted with a HEPA filter Dis...

Страница 4: ...eing incorrectly laid This should be checked prior to contacting a service engineer SECTION TWO Operation The full lighting procedure is as follows a Push slide control lever down as far as possible a...

Страница 5: ...oved CARE SHOULD BE TAKEN TO AVOID CONTACT WITH THE REFRACTORY LINING THIS IS A DELICATE SURFACE AND SHOULD NOT BE WIPED OR RUBBED FUEL BED LAYOUT COAL OPTION Coal set provided consists of 6 off shape...

Страница 6: ...and Layout Cont Place the first row of 3 x A and 3 x B overlay loose coals as shown between the front coals and base matrix Make sure that they are stable and DO NOT let them fall down in the gaps be...

Страница 7: ...EE Fuel Bed Cleaning and Layout Cont Add 2 x type B coals and 1 x type A as shown Add the final 3 x B coals as shown The layout is now finished Note Dye is available for touching up coal and liner boa...

Страница 8: ...ilation is provided it should be checked periodically to ensure freedom from obstruction Ventilation in the Republic of Ireland Must be permanent ventilation and must comply with the rules in force an...

Страница 9: ...IANCE MUST ONLY BE INSTALLED IN THE GB OR IRELAND Only to be used in sufficiently ventilated room Read instructions carefully before installation and use The appliance must be installed by a competent...

Страница 10: ...an be installed in the following flues and locations CLASS ONE A conventional brick or stone chimney as used for a solid fuel appliance with a typical effective cross sectional dimension of 225 x 225...

Страница 11: ...must be suitable for the purpose SECTION EIGHT Fireplace Requirements A flat face of 605 mm high x 500 mm wide must be provided around the fireplace opening for the fixing of the appliance to ensure...

Страница 12: ...on of the appliance ensuring it is very visible and it should be positioned at a height were it can clearly be seen on approach Frets and Fascias used for HOLE in the WALL must be compliant with C J F...

Страница 13: ...d normal adventitious room ventilation exists The installer must satisfy this point by carrying out a mandatory spillage test In the Republic of Ireland permanent ventilation must comply with the rule...

Страница 14: ...echanism is swung up to give easy access to the gas connection point as shown Cut a cross slit in the rubber grommet and feed the appliance onto the 8mm gas supply pipe Position the restrictor elbow s...

Страница 15: ...CE IS FITTED NOTE DO NOT USE PERMANENT SEALING COMPOUNDS i e SILICONE SEALANT THIS COULD CAUSE THE APPLIANCE TO BE DAMAGED WHEN IT IS REMOVED FOR SERVICING AND COULD INVALIDATE THE WARRANTY If a space...

Страница 16: ...e Users Section of these instructions ENSURE THE FUEL BED IS PLACED AS INDICATED IN THESE INSTRUCTIONS Flip the slide control lever round so that the rubber capped end is protruding out to the right a...

Страница 17: ...st should be repeated with the fan running If there is a connected room with an extractor fan the test should be repeated with all the doors to that room opened and the extractor fan running COMPLETIO...

Страница 18: ...he loose components have been removed Examine the fuel bed components for signs of cracking and replace if necessary IMPORTANT see fuel bed layout procedure before attempting to replace loose fuel bed...

Страница 19: ...peration 2 for removal of burner and or silencer 3 Disconnect gas connection to injector and gas control 4 Unscrew the locking nut fixing injector to mounting bracket 5 Clean or replace as necessary 6...

Страница 20: ...helpdesk Model UC Living Rosmore Slide Control Serial No This information can be found on the label attached to the packaging and on the data badge which is located on the appliance flange top right b...

Страница 21: ...nual service Engineer Name Gas Safe Registration No Date of Second annual service Engineer Name Gas Safe Registration No Date of Third annual service Engineer Name Gas Safe Registration No Date of For...

Страница 22: ...22 LT6587 Iss 1 10 13...

Страница 23: ...pliance must be installed by a Gas Safe registered person 2 The appliance must be used in accordance with the users instructions 3 The appliance must be serviced annually by a Gas Safe registered pers...

Страница 24: ...24 LT6587 Iss 1 10 13...

Страница 25: ...________________ Address ________________________________ Post Code TELEPHONE No PRODUCT DETAILS Model UC Living Rosmore Slide Control Serial No Date of Purchase This information can be found on the l...

Страница 26: ...LT Iss...

Страница 27: ...27 LT6587 Iss 1 10 13...

Страница 28: ...28 LT6587 Iss 1 10 13...

Страница 29: ...29 LT6587 Iss 1 10 13...

Страница 30: ...30 LT6587 Iss 1 10 13...

Страница 31: ...31 LT6587 Iss 1 10 13...

Страница 32: ...t Burner Tray Box Assembly Slide Control Trim Covers And Instructions Warning Label Fire Guard Fuel Bed Comprises of Base Matrix 4720 Bag Of Coals 6543 Front Coal LH 4723 Front Coal RH 4724 Restrictor...

Отзывы: