117
Xii. Troubleshooting
(continued)
C. Help Screen Faults
indication
Condition
Possible Cause
Zone Panel
Setup
Flashing
Zone Panel 1
Setup
Flashing
Zone Panel 1 communication lost, typical for Panel 1 through 4: The zone panel’s
communication was established and then lost. Check the following to correct the
issue:
• Wiring between panel and boiler.
• Zone panel DIP switch settings have changed:
- Set Master/Slave switch to “Master”
- Set Zone Control switch ZC1 to “ON”
- Cycle power
Zone Panel Electronics Failure: A Zone Panel
Duplicate Zone: The Control has detected duplicate zone panel numbers. Check the
following to correct:
• Each Zone Control DIP Switch must be set to a Unique setting:
Note that when multiple ZC switches are set on ON the Zone Panel
is reported as Zone Panel 1.
Sequencer
Setup
Sequencer
Setup
Fault
This alarm is active if the slave boiler has lost communication with the Sequence
Master. Check the following:
- RJ 45 peer-to-peer network disconnected
- Sequencer Master was Enabled and then Disabled
- Master’s Boiler has been powered down.
- To clear fault restore communication or cycle power
Boiler Size
Setup
Boiler
Size
Fault
Warning!
Boiler size setting may not match actual boiler size.
The Boiler size setting determines min, max and light-off blower speeds. Incorrect
boiler size can cause hazardous burner conditions and improper operation that may
result in PROPERTY LOSS, PHYSICAL INJURY, OR DEATH.
Refer to page 91 for boiler size setting instructions.
Zone Panel
Failure
Flashing
Duplicate
Zone
Flashing
D. Help Screen Diagnostic Features
indication
Possible Cause
Lockout History is stored in a first-in, first-out basis. Each History file is stored with boiler run hour of when the
lockout occurred.
The “When happened” and “Current” provide:
- “Current” is the run hour and status the boiler just finished.
- “When happened” is the run hour and status when the lockout occurred.
For Service Contact:
CONTRACTOR NAME
CONTRACTOR ADDRESS
1
CONTRACTOR ADDRESS
2
PHONE NUMBER
The user is given the contact information of the responsible service provider. Refer to page 97 for data entry
instructions.
Содержание Alpine ALP500C
Страница 14: ...14 III Pre Installation and Boiler Mounting H Boiler Stacking continued Figure 5 Boiler Stacking ...
Страница 48: ...48 VI Water Piping and Trim continued Figure 28 Near Boiler Piping Heating Only ...
Страница 60: ...60 Figure 37 PCB Locations for Field Wiring Figure 38 120 VAC Field Wiring VIII Electrical continued ...
Страница 62: ...62 Figure 40 Ladder Diagram VIII Electrical continued ...
Страница 63: ...63 VIII Electrical continued 2 Figure 41 Wiring Connections Diagram ...
Страница 67: ...67 VIII Electrical continued Figure 45 Boiler to Boiler Communication with Zone Control Circulator Panel ...
Страница 72: ...72 IX System Start up continued Figure 48 Operating Instructions ...
Страница 124: ...124 XIII Repair Parts continued ...
Страница 126: ...126 XIII Repair Parts continued ALP600C ALP700C and ALP800C ALP800C shown ...
Страница 130: ...130 XIII Repair Parts continued ...
Страница 133: ...133 XIII Repair Parts continued 10A 10B 10C 10D 10G ...
Страница 143: ...143 ...
Страница 144: ...144 U S Boiler Company Inc P O Box 3020 Lancaster PA 17604 1 888 432 8887 www usboiler net ...