XI. Service and Maintenance
(continued)
E. Condensate Overflow Switch and Condensate
Trap Removal and Replacement:
For removal or replacement of the condensate
overflow switch and/or condensate trap follow the
steps below. For parts identification, refer to Section
XIII “Repair Parts”.
1. Condensate Overflow Switch Removal and
Replacement:
a. Disconnect power supply to boiler.
b. Remove 2 wire nuts and disconnect overflow
switch wire pigtails from boiler wiring.
c. Using pliers, release spring clip securing the
overflow switch to condensate trap body and
remove the switch. Note that the switch has
factory applied silicon adhesive seal, which
may have to be carefully cut all around to
facilitate the switch removal.
d. Insure the trap overflow switch port is not
obstructed with silicon seal debris, clean as
needed.
e. Apply silicon sealant to the replacement switch
threads and install the switch into the trap
body making sure it is properly oriented - the
arrow molded into the switch hex end side
must face down for proper switch operation.
See Figure 47 “Condensate Overflow Switch
Orientation” for details.
f. Reconnect the switch wire pigtails to the boiler
wiring and secure with wire nuts.
g. Restore power supply to boiler. Fill up the trap
(see Section V “Condensate Disposal”) and
verify the switch operation.
2. Condensate Trap Removal and Reinstallation:
a. Disconnect power supply to boiler.
b. Remove 2 wire nuts and disconnect overflow
switch wire pigtails from boiler wiring.
Outdoor Temperature
Ohms of
Resistance
°F
°C
-20
-28.9
106926
-10
-23.3
80485
0
-17.8
61246
10
-12.2
47092
20
-6.7
36519
30
-1.1
28558
40
4.4
22537
50
10.0
17926
60
15.6
14356
70
21.1
11578
76
24.4
10210
78
25.6
9795
80
26.7
9398
90
32.2
7672
100
37.8
6301
110
43.3
5203
120
48.9
4317
Outdoor Air Temperature Sensor
Temperature versus Resistance
(P/N 102946-01)
(10kOhm NTC Sensor)
Header Temperature Sensor
Temperature versus Resistance
(P/N 101935-01 or 103104-01)
(10kOhm NTC Sensor), Beta of 3950
Temperature
Ohms of
Resistance
°F
°C
32
0
32648
50
10
19898
68
20
12492
77
25
10000
86
30
8057
104
40
5327
122
50
3602
140
60
2488
158
70
1752
176
80
1256
194
90
916
212
100
697
248
120
386
Temperature
Ohms of
Resistance
°F
°C
32
0
36100
50
10
22790
68
20
14770
77
25
12000
86
30
9810
104
40
6653
122
50
4610
140
60
3250
158
70
2340
176
80
1710
194
90
1270
212
100
950
230
110
730
248
120
560
Supply, Return and Stack Temperature
Sensor Temperature versus Resistance
(12kOhm NTC Sensor), Beta of 3750
Poison Hazard. Use
only inhibited propylene glycol solutions
specifically formulated for hydronic systems.
Do not use ethylene glycol, which is toxic and
can attack gaskets and seals used in hydronic
systems. Use of ethylene glycol could result in
property damage, personal injury or death.
WARNING
Содержание Alpine ALP080B
Страница 76: ...76 103448 10 6 18 VIII Electrical continued...
Страница 77: ...103448 10 6 18 77 VIII Electrical continued Figure 27 Wiring Connection Diagram...
Страница 78: ...78 103448 10 6 18 Figure 28 Ladder Diagram VIII Electrical continued...
Страница 82: ...82 103448 10 6 18 VIII Electrical continued Figure 29D Boiler to Boiler Communication with Zone Panel...
Страница 146: ...146 103448 10 6 18...
Страница 147: ...103448 10 6 18 147...
Страница 148: ...148 103448 10 6 18 U S Boiler Company Inc P O Box 3020 Lancaster PA 17604 1 888 432 8887 www usboiler net...