Thermistors

There are 3 thermistors used with the 3018/24 models.
• Zone Thermistor - Located on the right hand wall and is used to 

maintain temperature.

• Evaporator Thermistor - Located on the back of the evaporator 

plate and is used during defrost.

• Ambient Thermistor - Located in the base of the unit on the 

condenser and is used to monitor ambient air temperatures.

Viewing Temperature

Note: 

The display shows set point 

NOT

 the actual temperature.

The 3000 series is equipped with an advanced electronic display and 
control. Thermistor readings can be obtained through both the 
customer and service menu. The customer menu will display readings 
while using offset calculations. It is important to note that the system 
will use these adjusted readings when determining cooling and 
defrost cycles. The service menu will display the actual thermistor 
reading while disregarding offsets. 

Customer Menu

To view the adjusted temperature of each available thermistor, follow 
the steps below. 

1. Initiate the customer menu by holding Select 

 for 5 seconds.

2. Use Down 

 to scroll to “Actual Temperatures”.

3. Press select 

.

4. Use Up 

 or Down 

 to scroll through available information.

Service Menu

To view the actual temperature without having the offsets taken into 
consideration, follow the steps below. 

1. Initiate the service menu by holding both up 

 and Zone Toggle 

 for 5 seconds.

2. Use Up 

 or Down 

 to scroll to “Actual Temperatures”.

3. Press select 

.

Use Up 

 or Down 

 to scroll through available information.

Thermistor Calibration

While thermistors generally do not require calibration, over time 
contact corrosion and or element wear may make calibration 
necessary.

Calibration

To calibrate a thermistor one must first prepare an ice water of 
crushed ice and water in a suitable container. Allow the ice water 
temperature to stabilize for at least 5 minutes before beginning.

NOTICE

Offsets are preset at the factory to efficiently maintain 
product temperature. If modifying offset, existing values 
must be taken into consideration.

NOTICE

Customer Care must be notified before any changes are 
made to factory set offsets. Failure to notify Customer Care 
will void the warranty. 

1. Enter the service menu and record existing offset values for each 

thermistor to be calibrated. See page 

16

. Some models have a 

factory offset setting of 0.

2. Change offset of each thermistor to be calibrated to 0.

3. Enter “Actual Temps” through the 

Customer Menu

. See 

“Viewing Temperature”.

4. Submerge the thermistor in the ice water. The temperature read 

out through the menu should be 32°F. If different, record 
difference.

5. Enter “Offsets” through the service menu and set the value 

recorded in step 4 to the thermistor to be calibrated.

6. Enter “Actual Temps” through the 

Customer Menu

, the 

temperature readout should now be 32°F. If the readout is still 
incorrect reset the offset to 0 and perform steps 4 & 5 again.

7. Enter the “Offsets” menu and add the value recorded in step 1 to 

the new offset setting. For example, if after the ice water an offset 
of 1 was needed and the existing offset value recorded in step 1 
was -2 the new offset value would be -1. If the calculated value is 
outside the maximum range capable in the offset menu the 
thermistor must be replaced. The offset menu has a maximum 
range of -10 through 10. 

Note: 

If a mistake is made in the calibration process a “Factory 

Default” will restore offsets to their factory pre-set values. See 

page

17

Содержание U-3018RFOL-00

Страница 1: ...U 3024RGLOL 01 U 3018RGLOL 00 U 3018WCS 15 U 3024RGLS 00 U 3018RGLOL 01 U 3024BEVOL 00 U 3024RGLS 01 U 3018RGLS 00 U 3024BEVOL 01 U 3024WCOL 00 U 3018RGLS 01 U 3024BEVS 00 U 3024WCOL 01 U 3018RGLS 13...

Страница 2: ...pump both the unit and the drain pump regardless of the manufacturer must be returned to U Line To complete the damage claim process for the consumer please obtain the following information This info...

Страница 3: ...usting Temperature Settings 10 Interior Lighting 11 Error Notification 11 Customer Menu 11 Service Menu 13 USB Communication 18 Quick Guide 21 Convection Cooling 23 3000 Series Maintenance Leveling 24...

Страница 4: ...rical Grounding Required Never attempt to repair or perform maintenance on the unit until the electricity has been disconnected Never remove the round grounding prong from the plug and never use a two...

Страница 5: ...r Glass Shelves No U 3018RGLS 00 Right Hand Hinge Stainless Steel Glass Door Glass Shelves No U 3018RGLS 01 Left Hand Hinge Stainless Steel Glass Door Glass Shelves No U 3018WCOL 00 Right Hand Hinge G...

Страница 6: ...d Overlay Door Bins U 3024RFS 00 Right Hand Hinge Stainless Steel Solid Door Bins U 3024RFS 01 Left Hand Hinge Stainless Steel Solid Door Bins U 3024RGLOL 00 Right Hand Hinge Glass Overlay Door Glass...

Страница 7: ...everage Market Root Pantry Deli 1 0 0 2 36 42 1 2 U 3018RGLS 00 Deli Beverage Market Root Pantry Deli 1 0 0 2 36 42 1 2 U 3018RGLS 01 Deli Beverage Market Root Pantry Deli 1 0 0 2 36 42 1 2 U 3018WCOL...

Страница 8: ...rket Root Pantry Deli 0 0 0 2 36 42 1 2 U 3024RFS 00 Deli Beverage Market Root Pantry Deli 0 0 0 2 36 42 1 2 U 3024RFS 01 Deli Beverage Market Root Pantry Deli 0 0 0 2 36 42 1 2 U 3024RGLOL 00 Deli Be...

Страница 9: ...F set point 38 F fruits vegetables berries lettuce Pantry 34 F 70 F set point 42 F dry goods breads baking items spices seasonings Root Cellar 45 F 55 F set point 50 F root vegetables potatoes onions...

Страница 10: ...cluded If you work on more than one unit per service call please submit a separate claim for each unit U Line tracks all defects through warranty claims Please be specific on what repair was completed...

Страница 11: ...return a part or if you may field scrap it If U Line requires a defective part to be returned a prepaid shipping label will be included with your new replacement part When returning parts enclose a c...

Страница 12: ...n and or element wear may make calibration necessary Calibration To calibrate a thermistor one must first prepare an ice water of crushed ice and water in a suitable container Allow the ice water temp...

Страница 13: ...series of Mode Settings with a default value for each mode Each mode setting can be further customized by fine tuning the temperature set point See the table below for a description of each mode and...

Страница 14: ...ct to Select Exit Actual Temps The Actual Temps option displays the offset corrected temperature of each zone evaporator as well as ambient temperature 1 To view actual temperatures first select Actua...

Страница 15: ...to select Off 3 Press Select Off will begin to flash 4 Use Up or Down to change Off to On 5 Press Select to Confirm your selection The display will fade out as the unit enters Sabbath mode Sabbath re...

Страница 16: ...o access the Help menu select Help from the Customer Menu Use Up or Down to scroll through available information The Help screen displays the following Model U Line contact information Software versio...

Страница 17: ...ost communication to the display Check display cable Replace if necessary Zone T Open Zone thermistor circuit open Check connection Replace if necessary Evap T Open Evaporator thermistor circuit open...

Страница 18: ...ugh available information To exit the Input Status menu use Up to select Return to Menu and press Select to confirm Outputs Outputs is used to monitor the state of DC outputs To access Outputs 1 Use D...

Страница 19: ...layed and the main control board is functioning properly If an error is listed attempt to correct it before changing control board See troubleshooting for tips on correcting errors To access Self Test...

Страница 20: ...ify customer service will result in voiding of the manufacturer warranty Call U Line Customer Service for assistance Re Select Model allows the unit s model configuration to be modified Changing the u...

Страница 21: ...amed uline csv on the flash disk In the event the file already exists new data will automatically be appended to the end of the existing file The file is output in a comma delineated text format and m...

Страница 22: ...Showroom Mode 2 Press Select 3 Use Down to select Off and press Select Off will begin to flash 4 Press Up or Down to toggle between off and on 5 Press Select to confirm If set to on showroom mode will...

Страница 23: ...plugged in 19 Relay 5 unassigned 5 active inactive 2 Temperature of Zone in F C 20 Relay 6 unassigned 6 active inactive 3 Not used 21 Compressor relay 7 active inactive 4 Not used 22 Evaporator fan 1...

Страница 24: ...018 3024 ADJUST MODES PRESS AND RELEASE TO SCROLL THROUGH THE MODES 4 3036 ADJUST TEMPERATURE PRESS TO SELECT ZONE PRESS TO SET THE TEMPERATURE 3018 3024 ADJUST TEMP PRESS TO SET THE TEMPERATURE 5 303...

Страница 25: ...CH AND HOLD TO EXIT SHOWROOM MODE SCROLL DOWN TO EXIT TOUCH AND RELEASE TO EXIT SERVICE MODE CONFIGURES THE ON BOARD USB PORT FOR FLASH DRIVE OR PC LINK DISPLAYS THE NUMBER OF TIMES AN ERROR HAS OCCUR...

Страница 26: ...ate of the door switch In order to operate efficiently the evaporator fan blade and vents should be unobstructed and free of any dust buildup Evaporator Fan Replacement Should the evaporator fan need...

Страница 27: ...grille lock screws See below 3 Gently pull grille away from unit until it stops 4 Push grille rails towards the center of the unit to lift rails off lock screws 5 Pull grille free from unit Installin...

Страница 28: ...over extend or damage it during door alignment Overlay Models Removing Overlay 1 Open door completely 2 Remove gasket 3 Remove six screws seated in gasket pocket Stainless Models Removing Wrap 1 Open...

Страница 29: ...d component should activate deactivate with the switching of the relay If it does not see Component Testing on page 27 Inputs The main control monitors a number of thermistor inputs and switch states...

Страница 30: ...ow is an example of how to properly test a component for functionality An evaporator fan is used Condition Customer complains of the unit not cooling properly The main screen of the display lists an e...

Страница 31: ...oblem Airflow through the grill below the door in front cannot be obstructed Also the unit cannot be installed behind a closed door or in a closet The unit is too cold or freezing product Control set...

Страница 32: ...er to Quick Chill Section of this manual Control set too cold Refer to Adjusting Temperature Settings Section of this manual Review logged error codes Refer to Fault System Diagnosis Guide Section of...

Страница 33: ...the compressor inlet The compressor takes the low pressure vapor and compresses it increasing both pressure and temperature The hot high pressure gas is pumped through the discharge line and into the...

Страница 34: ...he unit will rely on a preset defrost timer during defrost cycles The unit will otherwise operate normally Evaporator thermistor errors are hidden from the display and recorded in All Errors and displ...

Страница 35: ...rm Extremely cold near inlet outlet below room temperature Lower than normal Partial Restriction Somewhat lower than normal in vacuum Warm near room temperature Very hot Top passes warm lower passes c...

Страница 36: ...nts or damage Repair split or pinched cabling Amb Thrm Short Inspect thermistor cable for pinch points or damage Replace if necessary Inspect wire harness from main control board for pinch points or d...

Страница 37: ...Captain Models Combo Models Refrigerator Freezers Refrigerators Drawer Models and Beverage Centers The U Line brand offers products in the 1000 Series 2000 Series and the Modular 3000 Series The 1000...

Отзывы: