PowerSeries Pro Installation Guide
Figure 1-8 SEOL wiring
Double end of Line (DEOL) resistors
When double end-of-line (DEOL) resistors are installed at the end of a
zone loop, the second resistor enables the panel to determine if the zone is
in open, closed, tampered or faulted.
Note:
Any zone programmed for Fire or 24-hr Supervisory must be wired
with a SEOL resistor regardless of the type of zone wiring supervision
selected for the panel. If you change the zone supervision options from
DEOL to SEOL or from NC to DEOL, power the system down
completely, then power it back up for correct operation.To enable DEOL
supervision per zone, program section [013], option [1] to OFF and option
[2] to ON. To configure DEOL supervision per zone, use programming
section [002], bit 11.
Figure 1-9 DEOL wiring
Triple end-of-line (TEOL) resistor
The TEOL resistor supervises anti-masking functionality in hardwired
motion detectors. To configure TEOL supervision per zone, use
programming section [002], bit 15.
Figure 1-10 TEOL wiring
Note:
Resistor values are configurable in section [004].
Bell wiring
These terminals supply 700 mA of current at 10.8 - 12.5 VDC for
commercial/ residential installations. To comply with NFPA 72 Temporal
Three Pattern requirements, section [013] Opt [8] must be ON. Note that
steady, pulsed alarms are also supported. Temporal 4 cadence for CO
alarm notification is also supported.
Figure 1-11 Bell wiring
The Bell output is supervised and power limited by 2 A hardware
protection. If unused, connect a 1000
Ω
resistor across Bell+ and Bell- to
prevent the panel from displaying a trouble.
Telephone line wiring
Wire the telephone connection terminals (TIP, Ring, T-1, R-1) to an RJ-
31x connector as indicated in the following diagram. For connection of
multiple devices to the telephone line, wire in the sequence indicated. Use
26 AWG wire minimum for wiring.
Figure 1-12 Telephone line wiring
Telephone format is programmed in option [350]. Telephone call
directions are programmed in options [311]- [318].
- 7 -