PowerSeries Pro Installation Guide
The product is labeled with the UL and ULC listing marks along with the SIA CP-01
compliance statement (Also Classified in accordance with SIA-CP-01 Standard) as proof
of compliance with the above mentioned standards. For further information on this
product’s listings please also refer to the official listing guides published at the UL web
site (www.ul.com) under Online Directions Section.
UL/ULC Residential Fire and Burglary Installations:
For ULC Installations, refer to the Standard for the Installation of Residential Fire
Warning Systems, CAN/ULC-S540.
l
Control Unit must be enclosed in model HSC3010C or HSC3020C enclosure.
l
Power supply model SOY-1800360NA (HS65WPSNA) must be employed.
l
24 h standby power must be provided for fire applications and 4h for burglary only
applications (AC trouble must be transmitted to SRC).
l
One DSC Model RM-1 or RM2 end-of-line supervision relay module must be used.
l
Priority of signals needs to be set Fire, CO/ Medical, Burg, Panic, AUX (Flood).
l
All burglary-type zones shall be configured with SEOL or DEOL configuration.
Use model EOLR-2
l
(refer to section [002], bit 10 or 11 shall be ON)
l
Use at least one PG9926/ PG9916/ PG9936 Smoke Detector for Fire Installations
(section [001], fire zone shall be programmed as type 025)
l
The entry delay shall not exceed 45 seconds (see section [005])
l
The exit delay shall not exceed 60 seconds (refer to section [005])
l
The minimum Bell Time-out is 4 minutes (refer to section [005])
Note:
Connect Bell output to a UL/ULC Listed audible device (e.g., UL File S8534,
model TS-443S-6), rated to operate over the range of 10.8 to 12.5 VDC and 85dBA
minimum. Wireless sirens PG9901 and PG9911 may also be used as audible devices.
Note:
For ULC Residential Fire installations, minimum bell time-out is 5 min. For UL
Home Health Care installations, minimum bell time-out is 5 min. For UL Commercial
Burglary installations, minimum bell time-out is 15 min.
l
Temporal Three Fire Signal shall be enabled (section [013], opt.8 ON)
l
Arm/Disarm Bell Squawk shall be enabled when using wireless key
PG4939/PG4929/PG4949 (section [014], option 1 shall be ON)
l
A code shall be required for bypassing (section [023], option 4 shall be ON)
l
Trouble beeps shall be enabled (section [022], option 7 shall be ON)
l
AC trouble indication LED shall be enabled (Keypad Programming, section [022],
options 5 and 6 shall be ON)
l
DACT Communicator shall be enabled for Supervising Station Monitoring (section
[380], option 1 shall be ON)
Note:
The DACT communicator for this product has no line security.
Telephone Line Monitoring (TLM) shall be enabled (section [015], option 7 shall be
ON)
This product is programmed to perform 5 attempts for communication of an event to the
supervising station. If unsuccessful, a Fail To Communicate (FTC) trouble is generated.
Test transmission cycle shall be set (refer to section [351]) for monthly transmission for
UL residential burglary applications and to 7 days for UL residential fire applications.
Note:
For ULC Residential/Commercial installations set for daily test transmission.
l
Wireless Supervision window shall be set to 4 hours for Fire Installations (Wire-
less Programming, section [804]>[802] shall be programmed with the value 16)
l
Wireless Supervision window shall be set to 24 hours for Burglary Installations
only (Wireless Programming, section [804]>[802] shall be programmed with the
value 96)
l
RF Jam detection shall be enabled (refer to Wireless Programming (section [804]
[801], option 00 shall be OFF)
l
New Alarms will Disconnect 2-way Audio (section [022], option 6 OFF)
ULC Commercial Burglary Security Levels I-IV:
The following wireless PowerG devices models are ULC listed under ULC-S304
requirements for use in Commercial Burg applications rated for security level 1.
l
PG9914
l
PG9905
l
PG9920
l
PG9975
l
PG9922
l
PG9924
l
PG9929
l
PG9934P
l
PG9935
l
PG9938
l
PG9939
l
PG9944
l
PG9945
l
PG9949
l
PG9974
l
PG9974P
l
PG9984
l
PG9984P
l
PG9985
l
PG9994
The wireless supervision window shall be set to 4h for such applications and the tamper
detection for removal from mounting location shall be enabled.
UL Central Station and Police Connect with Standard or Encrypted
Line Security Service
l
The installation must use the integral Ethernet communicator or the plug-in cellular
modules Models LE9080, 3G9080 or 3H9080, which communicates over Cellular
Data Network or an Ethernet network 10/100BaseT to the compatible Sur-Gard Sys-
tem I/II/III/IV/5 receiver.
l
Polling time shall be 200 seconds and compromise detection time shall be 6
minutes.
l
For Encrypted line security applications, the integral Ethernet communicator or the
plug-in cellular modules Models LE9080, 3G9080 or 3H9080 shall have the
Encryption Key enabled (AES128 bit encryption algorithm is validated under NIST
Certificate No.5371 and 5372.)
l
Wireless Supervision window shall be enabled (refer to Wireless Programming, sec-
tions [804]>[802].)
l
Open/Closing acknowledgment shall be enabled (Not required for Police Station
connected systems.)
l
Bell test for police station connect.
UL Local, Central Station and Police Connect with No Line Security
Service
l
All zones shall be programmed as end-of-line supervised.
l
All intrusion zones shall be programmed as audible.
l
The installation shall use a Bell UL Listed for Mercantile local alarms (e.g., Honey-
well Model AB-12M bell housing). Connections from the control unit to the bell
shall be made in conduit. (Optional for central Station).
l
The Bell shall be tested daily. Alternate option is to have bell squawk enabled for
arming/disarming. The Bell activation cannot be delayed for more than 5 mins.
l
The bell timeout shall be programmed for 15 minutes minimum.
l
At least one system remote keypad with tamper switch shall be employed
l
The integral communciator (DACT/IP) or plug-in cellular module shall be enabled
and shall be programmed to provide a low battery transmission.
l
The control panel shall be in a separately listed HSC3030CAR attack resistant
enclosure.
l
The maximum entry delay time shall not exceed 45s (25s for a local) as a result of
the attack test. The maximum exit delay time shall not exceed 60 s.
l
A tamper switch shall be used to protect the enclosure cover of the control unit. A
tamper switch shall also be used on the keypad rear to detect removal from the
wall.
l
24 h check in transmission shall be enabled.
l
Open/Closing acknowledgement enabled.(Not Police Station).
l
The Installation shall use the internal communicator (DACT or IP) alone or in con-
junction with plug-in cellular modules Models LE9080, 3G9080 or 3H9080, which
communicate over Cellular Data Network or an Ethernet network 10/100BaseT to
the compatible Sur-Gard System I/II/III/IV/5 receiver.
UL Home Health Care Signaling Equipment
l
There must be at least two keypads, one of the compatible keyapds models
HS2LCDPRO, HS2LCDRFPRO9, HS2LCDWFPRO9, HS2LCDWFVPRO9,
HS2TCHPRO(BLK).
l
Each system shall be programmed to activate an audible Trouble signal within 90
seconds upon loss of microprocessor memory
ULC Central Station Fire and Burglary Monitoring Installations
l
For installation requirements, levels of security, communication modules and con-
figurations (Refer to the ULC Installation Guide for PowerSeries Pro, P/N
#29010346).
l
HS2TCHPRO(BLK) touch screen keypad is for supplementary use only with ULC
Commercial Fire Monitoring.
l
For Commercial Fire monitoring, the primary power failure transmission may be
delayed up to 3h and Bell shall be disabled.
Note:
As per ULC Bulletin 2017-02A, ULC Fire and Security Systems Group is
accepting the use of MFVN digital telephone services for connection of digital dialer
transmitters ULC listed to be connected to the public switched telephone network
communication system. Since the MFVN communication channel technologies available
are not provided with 24 hour standby power on the equipment and facilities used
between the premises and the signal receiving center, it is required that, for passive
communication channels used in monitored protective signaling system installations, the
testing time of the passive communication channels should be reduced from the current
24 hours to 6 hours to better ensure that the system and communication channels are
operating in their intended manner to reduce the life safety risk. A change in testing
frequency for intrusion alarm systems is not required due to the many different levels of
line security options available for these system types, which should be applied based on
communication supervision needs for each installation.
For PowerSeries Pro panels, the following programming options shall be adjusted to
meet the new 6 hour test transmission when used in ULC-S561 compliant installations:
l
Section [022] turn option 4 ON for hours.
l
Section [377] option [003] set to 006 (for 6 hours).
l
Section [309] option [002] enable test transmission for all applicable receivers.
Programming
The notes in the programming sections of thePowerSeries Pro Reference Manual
describing the system configurations for UL/ULC listed installations shall be
implemented.
Control of the Protected Premises
In order to have a UL certificated system, the protected area shall be under the
responsibility of one ownership and management (i.e., one business under one name).
This may be a group of buildings attached or unattached with different addresses but
- 28 -