Document No: LT0255
F3200/NDU AS4428.1 Installation Manual
Applications
Issue 1.22
5 July 2016
Page 6-17
AVI Mk2 (Continued)
The configuration of some commonly used signs is as follows.
Function
Illuminate Tone
Polarity
Links
+/-
Fitted
Top:
FIRE ALARM
Top
Alert
IN-T/IN-B -
Bottom:
EVACUATE AREA
Both
Evac
IN-B/IN-T -
Top:
FIRE ALARM
Top
Alert
IN-T/IN-B -
Bottom:
DO NOT ENTER
Both
Evac
IN-B/IN-T -
Top:
DO NOT ENTER
Top
Evac IN-T/IN-B 3
Bottom:
XXXX GAS DISCHARGE
Both
Evac*
1
IN-B/IN-T 3
Both:
XXXX SYSTEM INOPERATIVE
Both
None
IN-B/IN-T 1, 2
*1 The AVI Mk2 has a third tone (RH3), which could be generated on Gas Discharged.
Refer to the particular AVI instructions for setting the links as the function of the links
depends on the software version fitted.
Options for XXXX include: CO2; INERGEN; FM-200.