Document No: LT0255
F3200/NDU AS4428.1 Installation Manual
Appendix A
Issue 1.22
5 July 2016
Page A-1
APPENDIX A1
COMPATIBLE ACTUATING DEVICES (DETECTORS)
The following detectors are compatible with the F3200 System. The maximum number of
detectors per circuit is indicated by the columns 4mA and IS, for Standard and Intrinsically
Safe applications. For IS application refer to Section 6.4.
DETECTORS CERTIFIED WITH F3200 FIP
MAX NO.
TYPE
DESCRIPTION
BASE
4mA
IS
614P
PHOTOELECTRIC SMOKE DETECTOR
5B or M614
38
-
614I
IONISATION SMOKE DETECTOR
5B or M614
40
-
614CH
CARBON MONOXIDE & HEAT DETECTOR
5B or M614
40
-
614TA
HEAT DETECTOR TYPE A
5B or M614
40
-
614TB
HEAT DETECTOR TYPE B
5B or M614
40
-
614TC
HEAT DETECTOR TYPE C
5B or M614
40
-
614TD
HEAT DETECTOR TYPE D
5B or M614
40
-
MD614A
HEAT DETECTOR TYPE A
5B or M614
40
-
MD614C
HEAT DETECTOR TYPE C
5B or M614
40
-
MF614
IONISATION SMOKE DETECTOR
5B or M614
40
-
MR614
PHOTOELECTRIC SMOKE DETECTOR
5B or M614
40
-
MR614T
PHOTOELECTRIC SMOKE DETECTOR
5B or M614
40*
1
-
MU614
CO FIRE DETECTOR
5B or M614
40
-
T614A or T614A Mk2
HEAT DETECTOR TYPE A
5B or M614
40*
2
-
T614B or T614B Mk2
HEAT DETECTOR TYPE B
5B or M614
40*
2
-
T614C or T614C Mk2
HEAT DETECTOR TYPE C
5B or M614
40*
2
-
T614D or T614D Mk2
HEAT DETECTOR TYPE D
5B or M614
40*
2
-
MF301Ex x
IONISATION SMOKE DETECTOR
M300
40
40
MR301Ex x
PHOTOELECTRIC SMOKE DETECTOR
M300
40
40
MR301TEx x
PHOTOELECTRIC SMOKE DETECTOR
M300
40
40
MS302Ex x
INFRA-RED FLAME DETECTOR
M300
40
40
MD601Ex
HEAT DETECTOR
5BEx
40
40
MDU601Ex
HEAT & CO DETECTOR
5BEx
40
40
MF601Ex
IONISATION SMOKE DETECTOR
5BEx
40
40
MR601TEx
HPO PHOTOELECTRIC SMOKE DETECTOR
5BEx
36
36
MU601Ex
CO DETECTOR
5BEx
40
40
601FEx
FLAME DETECTOR
5BEx
6
6
S111 x
INFRA-RED FLAME DETECTOR (IS)
-
40
35
S121 x
INFRA-RED FLAME DETECTOR (IS)
-
40
35
S131 x
INFRA-RED FLAME DETECTOR (IS)
-
40
35
S231i+ x
INFRA-RED FLAME DETECTOR (IS)
-
-
11
S231i+
INFRA-RED FLAME DET & ZAU401
-
5
5
S231f+
INFRA-RED FLAME DET & ZAU401
-
5
-
S261f+
INFRA-RED FLAME DETECTOR
-
40
-
FV411f/2f/3f
INFRA-RED FLAME DETECTOR
-
4
SU0600
15V MCP
-
40
-
*
1
For ambient temp < 30°C. Max Qty is 34 otherwise
*
2
47E resistor required between AZC+ and deve when using T614 (Mk1). See PBG0116.
Table I MINERVA/THORN/TYCO Detectors