PCN 504819-000
Effective Date: June 29, 2010
PII 54863
Revision AD
2
Installation Instructions
Table 1
PILC/Poly
PILC
Poly
Nominal
Insulation
Insulation
Maximum
Connector
Cable
Diameter
Diameter
Dimensions
Kit Range
Range Range
Length
Diameter
HVSA-3-1581S
#4-4/0
0.60-1.00 (15-25mm)
0.65-1.05 (17-27mm)
4.5 (115mm)
0.90 (23mm)
HVSA-3-1582S
4/0-350
0.85-1.10 (22-28mm)
0.90-1.30 (23-33mm)
5.5 (140mm)
1.15 (29mm)
HVSA-3-1583S
500-750
1.05-1.50 (27-38mm)
1.10-1.60 (28-41mm)
7.0 (178mm)
1.60 (41mm)
HVSA-3-1584S
750-1000
1.15-1.75 (29-44mm)
1.25-1.80 (32-46mm)
8.0 (203mm)
1.85 (47mm)
1. Product selection
Check kit selection with cable diameter dimensions in Table 1.
Note:
Table is for 100% insulated Poly cable. For 133% insulated
cable, check actual cable dimensions.
2. Check ground braid
Verify that ground braid(s) or bond wire have equivalent cross-
section to cable metallic shield. Additional braid may be needed
for LC shield, lead sheath cables, or if external grounding or shield
interrupting is required.
Raychem HVS-EG supplies ground braid, spring clamp and
suggested modifications to make an external ground or shield
interrupt.
3. Prepare cables
Choose the cable type (Choice 1-3) and use the dimensions shown in
Table 2 to prepare the cables.
Table
2
Metallic
Shield
Cutback/ Semi-con
Jacket
Cutbacks
Wire
Pullback
Cutback
Kit
A1
A2
B
C
HVSA-3-1581S
34” (863mm)
19” (483mm)
9” (229mm)
5-1/2” (115mm)
HVSA-3-1582S
33” (838mm)
20” (508mm)
10” (254mm)
6” (152mm)
HVSA-3-1583S
39” (990mm)
22” (559mm)
11” (279mm)
7” (178mm)
HVSA-3-1584S
38” (965mm)
23” (584mm)
12” (305mm)
7-1/2” (190mm)
Choice 1
If Metallic Tape Shield Cable
Refer to Table 2 and prepare the cables as shown. Remove any fillers
to the armor cutback. Bend back the grounding conductors(s) over
the jacket as shown.
Go to Step 4, page 3.
A2
PILC
A1
C
C
L
B
Grounding
Conductor(s)
P
OL
Y
4"
(102mm)
176