Technical data
Table 0.2c – Technical data of frequency converters of the
MFC710 690V
series, depending on a type
The type
MFC710/690/...
Constant-torque load
(max. overload 1.5)
P
N
[kW]
I
N
[A]
Variable-torque load
(max. overload 1.1
1)
)
P
N2
[kW]
I
N2
[A]
I
p
[A]
15kW
15
18
18
21
26
18,5kW
18
23
22
26
35
22kW
22
26
30
35
39
30kW
30
36
37
43
52
37kW
37
43
45
52
65
45kW
45
52
55
64
78
55kW
55
64
75
87
95
75kW
75
87
90
104
130
90kW
90
104
110
121
156
110kW
110
121
132
144
182
132kW
132
144
160
179
217
160kW
160
179
180
219
268
180kW
180
202
200
242
300
200kW
200
219
250
266
329
250kW
250
266
315
329
398
315kW
315
329
355
393
491
355kW
355
375
400
420
530
400kW
400
2)
400
420
530
500kW
500
2)
500
500
550
560kW
560
2)
560
560
615
630kW
630
2)
630
650
715
800kW
800
2)
800
800
920
1)
For ambient temperature < 35
0
C.
2)
For frequency converters at nominal power 400 kW and above, the range of overload is determined in
consultation with the Customer.
P
N
– nominal output power when the maximum overload current I
p
is about 1.5 I
N
(constant-torque load).
I
N
– nominal output current at P
N
.
P
N2
– nominal output power when the maximum overload current I
p
is about 1.1 I
N2
(pumps, fans).
I
N2
– nominal output current at P
N2
.
I
P
– overload current: 60 seconds every 10 minutes.
Installation figures
The dimensions of frequency converter, type MFC710.
Enclosure type A
Enclosure type B
Free space around
the converter
It is necessary to provide some free space around the converter for appropriate air circulation.
10
Frequency converter MFC710 type. TWERD Power Electronics
b
B
C
A
a
b
B
A
a
Ø1
Ø2
Ø1
d1
φ
Ø2
d2