Appendix C – Table of MFC710 frequency converter's parameters
Parameters
in group 0
Name
Description
0.48
DI state
State of all six digital inputs (for RS six youngest bits of the register)
0.49
DO state
State of all four digital output (for RS four youngest bits of the register)
0.50
RS1 state
Corresponds to the value written into the register 2000 through RS connection
0.51
Version
Version of the frequency converter software
0.52
RS ref.
RS referencing-unit. Corresponds to the value written into the register 2001 through RS [Hz]
or [rpm].
0.53
RS PID ref.
RS PID Ref.-unit. Corresponds to the value written into the register 2002 through RS [%]
0.54
U1 preview
Programmable User value number 1 (see section 11.4)
0.55
U2 preview
Programmable User value number 2 (see section 11.4)
0.56
U3 preview
Programmable User value number 3 (see section 11.4)
0.57
U4 preview
Programmable User value number 4 (see section 11.4)
0.60
Curr.Motor
Number of active motor
Parameters 0.70 ÷ 0.79 are active only in regenerative frequency inverters MFC710AcR
0.70
AcR I L1
Current of a phase L1 of the line [A]
0.71
AcR I L2
Current of a phase L2 of the line [A]
0.72
AcR I L3
Current of a phase L3 of the line [A]
0.73
AcR Ip
Active current of the line [A]
0.74
AcR Iq
Reactive current of the line [A]
0.75
AcR UL
Interfacial AC voltage the supply grid powering the converter [V]
0.76
AcR Temp1
Temperature of the active rectifier IGBT modules [
0
C]
0.77
AcR Temp2
Temperature of the active rectifier IGBT modules [
0
C]
0.78
AcR Fault code
AcR error code
0.79
AcR version
AcR software version
Parameters in group 1 ÷ 6
Parameter / Name
Function
Available options / measurement unit
Factory
setting
Change
during
operation
GROUP 1 – CONFIGURATION OF THE DRIVE
1.1 Pn
Nominal power of the
motor
0.0 ... 2 x [Nominal power of the freq. converter] kW
Nominal
power of the
frequency
converter
NO
1.2 Rn
Nominal motor speed
0 ... 30000 rpm
1450 rpm
NO
1.3 In
Nominal motor current
0.00 ... 2 x [Nominal current of the freq. converter] A
Nominal
current of the
frequency
converter
NO
1.4 Un
Nominal motor voltage
0 ... 1000 V
Nominal
voltage of the
frequency
converter
NO
1.5 fn
Nominal motor frequency
0.0 ... 550.0 Hz
50.0 Hz
NO
1.6 PF nom.
Nominal cos φ
n
of the
motor
0.50 ... 1.00
0.80
NO
1.10 ID run
Identification of motor's
equivalent circuit
parameters
000 ---
– without identification
001 Don't run
– only for stopped motor
002 Run 25Hz
– test at 25 Hz
003 Run 50Hz
- test at 50 Hz
000 ---
NO
1.11 Rs
Resistance stator windings 0 ... 32.000
0.000 Ohm
NO
1.12 Rr
Resistance of rotor
windings
0 ... 32.000
1)
Ohm – read only
0.000 Ohm
NO
1.13 Lm
Main inductance Lm
0.0 ... 3200.0
1)
mH
0.0 mH
NO
1.14 Ls
Stator inductance Ls
0.0 ... 3200.0
1)
mH
0.0 mH
NO
1.15 Lr
Rotor inductance Lr
0.0 ... 3200.0
1)
mH
0.0 mH
NO
1) The number of decimal places depends on the nominal power of frequency converter
78