background image

6

EN

CONTROL

 

MODULE

MAIN SCREEN

The main led screen is displayed when the power supply is on. On the left, the queue 

status is displayed (Q0 – queue for left direction, Q1 – queue for right direction). Errors 

are displayed in the upper right corner. Possible errors are:

• 

Enc_error – encoder error, not connected or damaged

• 

Lic_error – inactive license

• 

Default_sett – memory read incorrectly – factory settings loaded

In the bottom right corner the current version of software is displayed.

Press the encoder to continue to the main menu.

MAIN MENU

Currently  chosen  position  is  pointed  by  an  arrow.  Pressing  the  encoder  confirms 

the choice. 

Main menu positions: 

Parameters – current parameters preview

Settings – configuration of the device

Test mode 

Back – return to the main screen

PARAMETERS MENU

Items displayed in the parameters menu: 

Cycles – quantity of cycles completed by the device 

Motor I – motor measured current value

Enc – the position of the rotor encoder

Vel – current velocity of the rotor

Back – return to the main menu 

SETTINGS MENU

Language configuration

Choose the interface language.

Default setting: PL

Free entrance function

Set the free entrance in desired direction. Possible settings: 

OFF – free entrance off. Passage possible only after receiving an external signal.

ON – free entrance on. Device is unlocked in the desired direction

Default setting: OFF

Queue size  

Queue length is the maximum number of release signals sent at short intervals that can 

be stored in the device’s memory.

Values to choose from: 1-99

Default setting: 3

Opening time

The time is counted from the moment of receiving the release signal. After the expiration 

of the time the passage is blocked again. 

Possible values to choose from: 3-60 seconds.

Default settings: 6s

Input signals configuration

In. 1-4 setting defines the function of IN 1-2 and IN 3-4 inputs. Possible configurations:

open – short circuit results in releasing the rotor blockade

free – short circuit triggers the free entrance function

lock -  short circuit results in blocking the external signals 

Default setting: open

Содержание BA3 Series

Страница 1: ...1 SG BA3 BR2 GA SERIES DEVICES CONTROL MODULE User s Manual...

Страница 2: ...2 Complete documentation GENERAL INFORMATION PEDESTRIAN TRAFFIC CONTROL DEVICE CONTROL MODULE MONTAGE MAINTENANCE AND SERVICE TECHNICAL DRAWINGS EN...

Страница 3: ...3...

Страница 4: ...PICTOGRAMS CONFIGURATION 7 LICENSE MENU 7 TEST MODE 8 SG SERIES DEVICES 8 DESCRIPTION OF THE CONTROL MODULE TERMINALS 8 SETTINGS MENU 9 ZERO POSITION CONFIGURATION 9 CALIBRATION 10 FIRST RUN 10 BA3 BR...

Страница 5: ...g software without the device manufacturer s consent The manufacturer reserves the right to introduce changes or updates to the software All devices are supplied with a stored standard software descri...

Страница 6: ...of the rotor encoder Vel current velocity of the rotor Back return to the main menu SETTINGS MENU Language configuration Choose the interface language Default setting PL Free entrance function Set the...

Страница 7: ...enu allows you to insert the license key to unlock the license Submitting an in correct key results in a temporary blockade of this menu item Pictograms configuration Pictograms configuration submenu...

Страница 8: ...ck option In devices of the BA3 BR2 and GA series the mode is used only in devices equipped in the rotor s movement support system Caution While starting the test mode no person can be found within th...

Страница 9: ...for a trigger signal If this setting is different than the central one it is recommended to use this setting in combination with the free passage in that direction Default setting cen Fire alarm conf...

Страница 10: ...e when manually moving the arm 3 Check the connection of optical sensors menu parameters A 0 digit means that the barrier is interrupted while 1 means that the barrier is not interrupted 4 The zero po...

Страница 11: ...ETTINGS MENU Coils type There are two options for each coil NOR normal coil during power failure the rotor stays blocked REV reverse coil during power failure the rotor stays unblocked Default setting...

Страница 12: ...he device s motor to identify it s parameters Notice During the calibration nothing shall interrupt the rotor s movement Otherwise the procedure has to be repeated This option is not available in GA a...

Отзывы: