CONTROL

 

MODULE

CALIbRATION

After entering the calibration submenu, we can change certain operating parameters of 

the control algorithm. To edit an item, press the encoder knob. Then, by turning it, increase 

or decrease the edited value.

• 

k – influences the general movement speed If the arm has a tendency to pass the 

locked position and then to reverse, the parameter needs to be reduced; if the arm 

moves too slow, it needs to be increased.

• 

u min – influences the tightening speed If the arm does not reach the position set, 

what is signaled by starting the buzzer and a temporary locking of the arm, the pa

-

rameter needs to be increased. Reducing the parameter should be done if the arm 

has a tendency to pass the set position.

Save the set values by using save and exit option when leaving settings menu.

FIRST RUN

In order to provide safety during first run, follow the following rules:

1.  Before applying power to the device make sure that all cables are connected properly.

2. 

Connect an electromagnetic break and motor after checking the encoder operation (menu - parameters - encoder - the value

should change when manually moving the arm)

3. 

Check the connection of optical sensors (menu parameters). A ‚0’ digit means that the barrier is interrupted, while 1 means that the

barrier is not interrupted.

4. 

The zero positions are factory-set. In case you need to re-set them, disconnect the electric break and motor from the driver.

5.  Wrong connection of the encoder may cause the device to behave in an unpredictable way. Take extra safety precautions.

bA3/bR2/GA SERIES DEVICES

DESCRIPTION OF THE CONTROL MODULE TERMINALS

Symbol

Description

IN 1-2

External signal input for right direction (NO). This input’s function is configurable. By 

default it’s configured as permission to pass (see the software documentation).

IN 3-4

External signal input for left direction (NO). This input’s function is configurable. By 

default it’s configured as permission to pass (see the software documentation).

IN 5-6

Permission signal input for left passage direction (NO).

IN 7-8

Permission signal input for right passage direction (NO).

IN 9-10

Fire alarm signal input. The signal can be configured NO or NC in the driver’s settings. 

After receiving a fire alarm signal the device turns on free passage mode for both 

passage directions

IN 11-12

Blockade signal input. Short circuit triggers the blockade – the device doesn’t react to 

release signals.

Содержание BA3 Series

Страница 1: ...1 SG BA3 BR2 GA SERIES DEVICES CONTROL MODULE User s Manual...

Страница 2: ...2 Complete documentation GENERAL INFORMATION PEDESTRIAN TRAFFIC CONTROL DEVICE CONTROL MODULE MONTAGE MAINTENANCE AND SERVICE TECHNICAL DRAWINGS EN...

Страница 3: ...3...

Страница 4: ...PICTOGRAMS CONFIGURATION 7 LICENSE MENU 7 TEST MODE 8 SG SERIES DEVICES 8 DESCRIPTION OF THE CONTROL MODULE TERMINALS 8 SETTINGS MENU 9 ZERO POSITION CONFIGURATION 9 CALIBRATION 10 FIRST RUN 10 BA3 BR...

Страница 5: ...g software without the device manufacturer s consent The manufacturer reserves the right to introduce changes or updates to the software All devices are supplied with a stored standard software descri...

Страница 6: ...of the rotor encoder Vel current velocity of the rotor Back return to the main menu SETTINGS MENU Language configuration Choose the interface language Default setting PL Free entrance function Set the...

Страница 7: ...enu allows you to insert the license key to unlock the license Submitting an in correct key results in a temporary blockade of this menu item Pictograms configuration Pictograms configuration submenu...

Страница 8: ...ck option In devices of the BA3 BR2 and GA series the mode is used only in devices equipped in the rotor s movement support system Caution While starting the test mode no person can be found within th...

Страница 9: ...for a trigger signal If this setting is different than the central one it is recommended to use this setting in combination with the free passage in that direction Default setting cen Fire alarm conf...

Страница 10: ...e when manually moving the arm 3 Check the connection of optical sensors menu parameters A 0 digit means that the barrier is interrupted while 1 means that the barrier is not interrupted 4 The zero po...

Страница 11: ...ETTINGS MENU Coils type There are two options for each coil NOR normal coil during power failure the rotor stays blocked REV reverse coil during power failure the rotor stays unblocked Default setting...

Страница 12: ...he device s motor to identify it s parameters Notice During the calibration nothing shall interrupt the rotor s movement Otherwise the procedure has to be repeated This option is not available in GA a...

Отзывы: