Commissioning
Connecting the device to a Modbus master
82
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
7.7.4
Setting Modbus channels (registers)
Set channel 0 (input data)
Double-click the Modbus TCP slave.
Select in the
Modbus Slave Channel
tab
Ò
Add channel
.
Enter the following values:
n
Name of channel
n
Access type: Read holding registers
n
Offset: 0x0000
n
Length: 64 registers (128 bytes)
Confirm with
OK
.
Fig. 79: Setting the READ register