D301271 1013 - FGEN - multi protocol
9-7
Modbus registers
9.3
Modbus registers
Note
shows the register mapping for the different Modbus addressing
methods.
Table 9-3:
Ident number of
the station
Address (hex.)
Access
A
Description
A
ro = read only
rw = read/write
0x0000 to 0x01FF
ro
packed process data of inputs
(process data length of the modules
→
(process data length of the stations
)
0x0800 to 0x09FF
rw
packed process data of outputs (process data length of
the modules
→
(process data length of the stations
)
0x1000 to 0x1006
ro
Station Identifier
0x100C
ro
Station status (see
)
0x1012
ro
process image length in bit for the intelligent output
modules
0x1013
ro
process image length in bit for the intelligent input
modules
0x1017
ro
Register-mapping-revision
(always 1, if not, mapping is incompatible with this
description)
0x1020
ro
watchdog, actual time [ms]
0x1120
rw
watchdog predefined time [ms] (default: 0), see also
Error behavior of outputs (watchdog) (page 9-20)
)
0x1130
rw
Modbus connection mode register,
0x1131
rw
Modbus connection timeout in sec. (Def.: 0 = never),
0x113C to 0x113D
rw
Modbus parameter restore,
(reset of parameters to default values)
0x113E to 0x113F
rw
Modbus parameter save,
(permanent storing of parameters)
0x1140
rw
deactivate protocol
Deactivates explicitly the selected Ethernet-protocol:
0 = EtherNet/IP™
1 = Modbus/TCP
2 = PROFINET
15 = web server
Содержание FGEN-AIM Series
Страница 1: ...USER MANUAL FGEN AIM stations with multi FUNTIONALITY Sense it Connect it Bus it Solve it...
Страница 8: ...D301271 1013 FGEN multi protocol vi...
Страница 14: ...About this manual D301271 1013 FGEN multi protocol 1 6...
Страница 42: ...Digital inputs FGEN IM16 x001 D301271 1013 FGEN multi protocol 4 4...
Страница 46: ...Digital outputs FGEN OM16 x001 D301271 1013 FGEN multi protocol 5 4...
Страница 104: ...Application example FGEN for EtherNet IP with Allen Bradley PLC and RS Logix 5000 D301271 1013 FGEN multi protocol 8 14...
Страница 126: ...Implementation of Modbus TCP D301271 1013 FGEN multi protocol 9 22...
Страница 186: ...Guidelines for Electrical Installation D301271 1013 FGEN multi protocol 13 8...